单选题 系统接线如图所示,各元件参数为G 1 、G 2 :30MVA, ;T 1 、T 2 :30MVA,U k %=10;选S B =30MVA时,线路标幺值为X L =0.3,X 0 =3X L 当系统在f点发生A相接地短路时,短路点短路电流为______kA.
【正确答案】 B
【答案解析】[解析] (1)计算各元件电抗,选S B =30MVA,U B =U aV
发电机G 1 :E 1 =1, ,X G1(2) =x (2) =0.1
发电机G 2 :E 2 =1, ,X G2(2) =x (2) =0.1
变压器T 1 ,T 2 线路L:X L(1) =X L(2) =X L =0.3,X 0 =3X L =0.9.
(2)根据已知各元件的序参数,绘制该系统故障后的序网,如下图所示.

(3)计算两端口网络参数.
正序等效电抗为:X 1∑ =x 11 ||X 21 =0.2||0.5=0.142857
负序等效电抗为:X 2∑ =x 12 ||x 22 =0.2||=0.5=0.142857
零序等效电抗为:X 0∑ =x 10 ||X 20 =0.1||(0.9+0.1)=0.0909

(4)短路处各序电流的计算.由于是单相接地短路,复合序网是三序网的串联,则:
,短路电流有名值: