期刊文献+

“Gold light”轮辅锅炉停炉后炉膛内壁“发红”故障分析 被引量:1

Analysis on a Failure of Which A Donkey Boiler's Furnace Wall Still "Red" after Shutdown
下载PDF
导出
摘要 "Gold light"轮辅锅炉停炉后,炉膛内壁有"发红"现象,导致光敏电阻探测到所谓的余光后,就会发生火焰探测器故障误报警——"FLAME EYE ABNORMAL"报警。该故障困扰管理人员多时,由于管理人员忽视船舶自动化控制设备的老化原因,控制参数与实际参数发生较大的差异,因此未能彻底解决问题;经过反复几次查找故障原因,才得以彻底地解决。 After A donkey boiler shutdown,the furnace wall was still "red" leading to photosensitive resistor detecting "light" that made flame detector to abnormal alarm — "FLAME EYE ABNORMAL" alarm.The management staff has been troubled by the failure,because they neglected the reasons for the aging of the ship automatic control equipment;the reasons made the control parameters and the actual parameters to have larger error occurrence of large changes in parameters,so they didn t completely solve the problem;After t...
作者 张守俊 李斌
出处 《青岛远洋船员学院学报》 2009年第2期41-43,共3页 Journal of Qingdao Ocean Shipping Mariners College
关键词 发红 火焰探测器 故障报警 燃油粘度 自动控制 red flame detector failure alarm fuel viscosity automatic control
  • 相关文献

参考文献1

  • 1蓝天等编著,王庆有.光电技术[M]电子工业出版社,2005.

同被引文献5

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部