良导体地线限制超高压输电系统工频过电压的作用 被引量:3

Effect of ACSR on Suppressing Power Frequency Overvoltage of EHV Transmission System
下载PDF
导出
摘要 通过比较不同型号良导体地线的波阻抗,分析了零序阻抗对不对称接地工频过电压的影响。计算了各种采用光缆复合架空地线情况下线路的工频过电压。指出利用良导体地线降低工频过电压可以减小线路并联补偿容量,降低安装成本和维护费用。最后分析了良导体地线降低工频过电压的制约因素。 The influence of zero-sequence impedance on power-frequency overvoltage of asymmetric eathing fault is researched though comparing surge impedance of different types of ACSR as ground-return wires. The power-frequency overvoltage is calculated in various conditions with OPGW. It is lower for the smaller surge impedance of ACSR consequently, parallel compensation capacity could be decreased to save the cost. The restrictions of using ASCR to limit power-frequency overvoltage are analyzed too.
出处 《高压电器》 CAS CSCD 北大核心 2004年第3期186-188,共3页 High Voltage Apparatus
关键词 工频过电压 良导体地线 零序阻抗 power-frequency overvoltage aluminum clad steel reinforced(ACSR) zero-sequence impedance