铅酸蓄电池室燃爆事故分析及其安全对策 被引量:8

Fault Analysis on Deflagration in the Lead-acid Storage Battery Chamber and Its Countermeasure
下载PDF
导出
摘要 通过对铅酸蓄电池室燃爆事故树定性分析 ,找出了可能导致铅酸蓄电池室燃爆事故发生的基本原因事件 ,即无通风设施 ,通风设施损坏 ,未及时送、排风 ,使用不防爆电器 ,防爆电器损坏 ,电气连接处接触不良 ,人体静电放电 ,室内吸烟 ,室内动火。为了预防铅酸蓄电池室燃爆事故的发生 ,关键是 :一要采取有效的通风措施 ,保持蓄电池室通风良好 ,使氢气浓度不能达到爆炸极限 ;二要采取防止火源发生的措施 ,使蓄电池室无点火源 ,只要蓄电池室内无火源 ,即使氢气浓度达到爆炸极限 ,也不可能发生燃爆。为了达到上述两个要求 。 By qualitative fault tree analysis of the lead-acid storage battery deflagration accident, it is possible to find out elementary events inducing the deflagration accidents, i.e. no ventilation installation, the failure of ventilation installation, no timely ventilation, not using unexplosive electric devices, damage of unexplosive devices, failure of lap joint of electrical devices, discharge of static electricity in human body, smoking in the room, using fire in the process of repairing. For prevention of deflagration in the lead-acid storage battery chamber, the key points are as follows. First, effective ventilation must be kept in the storage battery chamber, which would keep the hydrogen concentration from reaching the explosion limit. Second, the fire source must be cut in the storage battery chamber. Without fire source, even if the hydrogen concentration reaches the explosion limit, it still could induce explosion. In order to fulfill two above-mentioned requirements, safety measures must be taken in respect of fire-proof and anti-explosion techniques and relevant management must also be reinforced.
作者 李发荣
出处 《中国安全科学学报》 CAS CSCD 2004年第8期79-81,共3页 China Safety Science Journal
关键词 铅酸蓄电池 蓄电池室 防爆电器 放电 电气连接 损坏 点火源 燃爆事故 吸烟 通风措施 Storage battery chamber Deflagration Fault tree analysis Prevention Safety countermeasure
  • 相关文献

参考文献3

  • 1崔国璋 韩军 周惠丰.事故树分析与应用[M].北京:机械工业出版社,1988.41-75.
  • 2GB50229-1996.火力发电厂与变电所设计防火规范[S].[S].,1996..
  • 3SDJ278-1990.水利水电工程设计防火规范[S].[S].,1990..

共引文献1

同被引文献47

引证文献8

二级引证文献34

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部