摘要 降低高土壤电阻率地区大型变电站接地电阻受到普遍关注,介绍了浙江绍兴500kV兰亭枢纽变电站接地网设计和首次改造的概况,讨论了降低接地电阻值的效果,对现行电力行业标准中规定的接地网不能满足R≤200/I时要求采取防止转移电位、验算接触电位差及跨步电位差等措施进行了分析。 To reduce the ground resistance of large substations in areas with high soil resistivity is attracting much attention. The ground grid design of 500 kV Lanting load-center substation in Shaoxing of Zhejiang is introduced, as well as its first retrofit. The effect of the reduction of the ground resistance is also discussed. It is stipulated in the prevailing electric industry standards that when the ground grid does not meet the requirement of R≤200/I, the measurements of preventing transferred potential, calculating contact-potential difference and step potential difference should be adopted. The above measurements are analyzed.
出处 《华东电力》 北大核心 2005年第7期88-90,共3页 East China Electric Power
关键词 大型变电站 接地网 接地电阻 large substation ground grid ground resistance
  • 相关文献

参考文献2

  • 1DL/T621—1997.交流电气装置的接地[S].[S].,..
  • 2Xu Feiwu. The Discussion on Earth - Resistance of 500 kV LanTing Substation [ C ], ICEE2001 Proceedings of International Conference on Electrical Engineering.

共引文献4

同被引文献6

  • 1DL/T621-1997.交流电气装置的接地[S].[S].,1997..
  • 2Xu Feiwu. The discussion on earth resistance of 500 kV Lanting substation[C]. ICEE2001 Proceedings of International Confer ence on Electrical Engineering. Xi'an, China, 2001.
  • 3清华大学电机工程与应用电子技术系.500kV兰亭变电站接地电阻测试及分析报告[R].北京:清华大学电机工程与应用电子技术系,1999.
  • 4DL475-92接地装置工频特性参数的测量导则[S].1992.
  • 5DZ/T0072-1993电阻率测深法技术规程[S].1993.
  • 6袁锦平.三种深井接地方式的适用性[J].广东电力,2003,16(2):17-19. 被引量:6