期刊文献+

办公室个性化送风气流性能评价 被引量:7

Evaluation of Air Distribution Performance of Personalized Ventilation System in Offices
原文传递
导出
摘要 通过改变个性化送风的送风距离、送风温度和送风速度,模拟分析了五种工况下的人员座位区的温度场和速度场.结果表明,适当的调整个性化送风的送风距离,既有助于减小对人员的冷吹风感,又能达到节能的效果,模拟得出的最佳送风距离为20~40cm. Based on the different air supply distances, air temperatures, and air velocities of personalized ventilation, the temperature and velocity distributions of occupant zones under five working conditions have been simulated. The results show that properly adjusting the air supply distance is helpful to solve cold draft problem and also achieves energy saving effect. The optimum air supply distances simulated range from 20 to 40 cm.
出处 《建筑科学》 北大核心 2005年第5期40-43,共4页 Building Science
关键词 个性化送风 送风距离 冷吹风感 节能 personalized ventilation air supplying distance cold draft problem energy saving
  • 相关文献

参考文献4

  • 1Stymne H, Sandberg M, Mattsson M. Dispersion Patter of Contaminants in a Displacement Ventilation Room[A]. Proceedings of the 12th AIVC Conference[C]. 1991.
  • 2端木琳,舒海文,杜国付.工位空调送风气流微环境评价[J].暖通空调,2004,34(12):7-9. 被引量:14
  • 3Melikov A K, Cermak R, Mayer M. Personalized Ventilation: Evaluation of Different Air Terminal Devices [J]. Energy and Buildings,2002, 34 (8): 829 - 836.
  • 4Toftum J, Zhou G, Melikov A. Effect of Air- Flow Direction on Human Perception of Draught [A]. Proceedings of CLIMA 2000 Brussels[C]. Session 1, 1997.

二级参考文献3

共引文献13

同被引文献40

引证文献7

二级引证文献9