摘要
石门电厂的XDPS-400系统,在控制逻辑的处理过程中发生了因执行顺序问题而导致炉膛灭火。通过对一次指令突变情况的模拟仿真和全面分析,提出了对时序问题的解决办法,并对XDPS-400系统中的模拟仿真提出了看法。
The XDPS--400 system of Shimen Thermal Power Plant, because of improper time sequence during logic control process, causes MFT of the boiler. Through simulation and overall analysis, the solution of the time sequence problem is put forward and the author also gives his own point about XDPS--400 simulation.
出处
《湖南电力》
2005年第5期15-16,19,共3页
Hunan Electric Power