期刊文献+

城市原生污水源热泵系统运行工况与参数特性 被引量:35

Operating Condition and Parameter Characteristic of Urban Wastewater Source Heat Pump System
下载PDF
导出
摘要 基于工程实践,在一定的技术背景条件下,对污水源热泵系统的制热、制冷工况及特征参数做了全面测试,包括供暖空调效果、水源侧运行参数、系统能耗水平、典型工况等,得到各类运行参数特性曲线.研究表明,热泵系统运行效果良好,水源侧温度保持在7℃以上,全系统制热系数大于3.5,制冷系数大于4.0,典型水源工况为7.5~3℃.对污水源热泵系统设计与评价有参考意义. From the engineering practice, under some technology background, the characteristic parameters of heating and refrigeration status was roundly tested, including the heating or air condition effect, the wastewater' s parameters, the system' s energy wasting level, typical work status. The characteristic curves of each work parameter was given out. The study indicated that the work effect is good and the wastewater' s temperature is above 7℃, the heating COP is above 3.5, the air condition COP is above 4.0, the typical wastewater temperature was 7.5 - 3℃. It's useful for designing or evaluating the wastewater source heat pump.
机构地区 哈尔滨工业大学
出处 《流体机械》 CSCD 北大核心 2005年第11期73-76,19,共5页 Fluid Machinery
基金 黑龙江省科技攻关项目(04GCZ1474)
关键词 城市原生污水 热泵系统 运行工况 参数特性 urban untreated wastewater heat pump system operating conditions parameter characteristic
  • 相关文献

参考文献11

二级参考文献14

  • 1-.城市统计年鉴[M].北京:中国统计出版社,1996..
  • 2落藤澄.寒冷地におけゐ都市排热および未利用エネルギ-の活用と评价[J].空气调和.卫生工学,2000,69:817-821.
  • 3中华人民共和国发展计划委员会基础产业发展司.1999年白皮书-中国新能源与可再生能源[M].北京:中国计划出版社,2000..
  • 4城市统计年鉴,1996年
  • 5下水道多目的活用研究会.下水道最先端一下水道の多目的活用[M].东京:理工图书株式会社,1997.
  • 6大迫健一.全国初の下水(未处理)を利用した地域冷暖房[J].建筑设と偏配管工时,1993,12(5):269-275.
  • 7伊均,陈雷.城市污水的资源再生及热能回收利用[M].北京:化学工业出版社,2003.
  • 8尹军.城市污水中的热能回收与利用[J].中国给水排水,1998,14(2):53-54. 被引量:36
  • 9尹军,韦新东.我国回收污水中热能的可行性分析[J].中国给水排水,2000,16(3):28-30. 被引量:43
  • 10尹军,韦新东.我国主要城市污水中可利用热能状况初探[J].中国给水排水,2001,17(4):27-30. 被引量:48