期刊文献+

GIS隔离开关带分合闸电阻抑制VFTO的研究 被引量:43

Suppression of VFTO by Disconnector with Opening and Closing Resistor in GIS
下载PDF
导出
摘要 针对超高压GIS中开关操作或发生接地故障时产生特快速暂态过电压(VFTO)从而影响GIS及其连接设备和二次控制设备的问题,根据800 kV GIS结构特别是母线较长(采用分布参数模拟,并考虑频率特性)的特点,利用EMTP程序对28种接线方式进行数值仿真计算。结果表明:隔离开关装和不装分合闸电阻(500Ω)时VFTO最大幅值分别为1.2932、.976 p.u.;该电阻>200Ω时可抑制VFTO,使其幅值<1.7 p.u.。故800 kV GIS中VFTO幅值对设备绝缘的影响很小,这对于GIS及其连接设备和二次控制设备的绝缘设计非常重要。 During switching operation or earth faults in SF6 gas insulated switchgear (GIS), Very Fast Transient Over-voltage (VFTO) occurs and will stress adjacent equipment or secondary equipment in GIS. With the increasing of GIS voltage level, the effect of VFTO should be taken more consideration. According to the characteristics of 800 kV GIS structure, especially when busbar is relative long (use distribution data simulation with taking into account the frequency characteristic), this paper had made data analysis to 28 deferent connection modes using EMTP program. The calculation effect shows that when open/close resistance on the disconnector is installed or not, the Max. amplitude of VFTO is 1. 293 p. u. and 2. 976 p. u. respectively. Data show that since the open/close resistance of disconnector has limited effect on VFTO, the amplitude of the VFTO is not high in GIS. When the open/close resistance is larger than 200 Ω, the amplitude of VFTO can be restrained under 1.7 p. u.. The amplitude of VFTO has little effect on equipment insulation. This is very important for the insulation design of the adjacent equipment and secondary equipment of 800 kV GIS.
作者 阮全荣 施围
出处 《高电压技术》 EI CAS CSCD 北大核心 2005年第12期6-8,共3页 High Voltage Engineering
关键词 GIS VFTO分合闸电阻 隔离开关 GIS VFTO opening and closing resistor disconnector
  • 相关文献

参考文献10

  • 1何善庆.GIS中的快速暂态现象[J].高压电器,1995,31(2):41-46. 被引量:52
  • 2钟连宏,欧世尧,周红霞.GIS中快速暂态过电压的分析及计算[J].高电压技术,2000,26(1):60-62. 被引量:46
  • 3Povh D,Schmitt H,Valcker O.Modeling and analysis guidelines foe very fast transients[J].IEEE Trans on PWRD,1996,11(4):2028-2035.
  • 4史保壮,李智敏,张文元,邱毓昌.超高压 GIS 中快速暂态过电压造成危害的原因分析[J].电网技术,1998,22(1):1-3. 被引量:71
  • 5张重远,梁贵书,崔翔,吴茂林.GIS隔离开关操作对二次设备的影响[J].高电压技术,2002,28(2):5-7. 被引量:53
  • 6Ozawa J,Yamagiwa T,Hosokawa M,et al.Suppression of very fast transient overvoltage during gas disconnector switching in GIS[J].IEEE Trans on PWRD,1986,1(4):194-201.
  • 7Yanagata Y,Tanaka K,Nishiwaki S,et al.Suppression of VFT in 1 100 kV GIS by adopting resistor-fitted disconnector[J].IEEE Trans on PWRD,1996,11(2):872-880.
  • 8Murayama Y,Kobayashi N,Nishiwaki S,et al.800 kV GIS design and field measurements for transient overvoltage[C].8th International Syrnposium on High Voltage Engineering.Yokohama,Japan,1993:23-27.
  • 9Grandl J,Meppelink J,FrOhlich K,et al.Studies of very fast transients(VFT) in a 765 kV substation[C].International Conference on Large High Voltage Electric Systems.Paris,France,1988.
  • 10国家电网公司.750 kV变电所设计暂行技术规定(电气部分)[S].北京:国家电网公司,2003..

二级参考文献12

  • 1何善庆.GIS中的快速暂态现象[J].高压电器,1995,31(2):41-46. 被引量:52
  • 2张纬钹,电力系统过电压与绝缘配合,1988年
  • 3Boersma R. Transient ground potential rises in gas insulated substations with respect to earthing systems. Electra, 1987, 110:47
  • 4Dick E P, Fujimoto N, Ford G L, Harvey S. Transient ground potential Rises in gas insulated substations-problem identification and mitigatioo. IEEE Trans PAS, 1982,101(10):3610
  • 5Sahni A M, Baliga C, Raina D, Tiku J K. Site investigations and study of very fast transient overvoltages in 245 kV gas insulated switchgear of tata electric companies. CIGRE, 1996,15(21):33
  • 6Heimbach M. VFT studies on current and voltage transformers in GIS by means of an iterative pole-zero-removal method for simulating the transfer function, In:Ninth International Symposium on High Voltage Engineering, August 28-September, 1995:6752
  • 7Nitzschke D, Bauer H. Simulation of transient disturbance voltages in substations using a combination of MoM and TLT, In:EMC Zurich 2001, 40G7
  • 8Daniel Tabara. Effets electromagnetiques de manoeuvres et de la foudre dans les postes sous enveloppe metallique:(Ph. D Thesis). Lausanne: the Technology Institute of Lausanne, Switzerland, 1999
  • 9史保壮,张文元,顾温国,邱毓昌.GIS 中快速暂态过电压的计算及其影响因素分析[J].高电压技术,1997,23(4):19-21. 被引量:31
  • 10钟连宏,贺景亮.GIS暂态地电位升高的计算与分析[J].高电压技术,2000,26(6):43-45. 被引量:18

共引文献177

同被引文献424

引证文献43

二级引证文献298