500kV变电站运行方式及工频相角对雷电侵入波过电压的影响 被引量:2

Effect of 500 kV substation operation mode and phase angle of applied voltage on lightning incoming surge
下载PDF
导出
摘要 雷电侵入波过电压是对500 kV变电站电气设备绝缘构成威胁的主要方式之一。选取典型500 kV变电站,分析了杆塔与绝缘子的计算模型,并应用ATPD raw仿真软件计算500 kV变电站运行方式与工频电压相角对雷电侵入波过电压的影响。 Lightning incoming surge is one of the main causes that damage the insulation of the high voltage apparatus io 500kV substations. In this paper, a traditional 500kV substation is illustrated. The calculation models of tower and suspension insulator are analyzed. ATPDraw simulation software is used to calculate the effect of 500 kV substation operation mode and phase angle of applied voltage on the over-vohage caused by lightning incoming surge.
出处 《湖南电力》 2006年第2期5-8,共4页 Hunan Electric Power
关键词 雷电侵入波 过电压 运行方式 工频相角 ATPDRAW lightning incoming surge overvoltage, operation mode phase angle ATP Draw
  • 相关文献

参考文献5

二级参考文献10

  • 1谷定燮,周沛洪,李国兴,梁志勇.取消500kV断路器合闸电阻有关问题的研究[J].中国电力,1996,29(6):28-32. 被引量:18
  • 2[2]IEC71-2 International standard insulation coordination-Part 2: Application guide. 1996.12
  • 3[3]Eriksson A and Weck K. Simplitied procedures for determining representative substation impinging lightning overvoltages. CIGRE paper No. 33- 16,Paris, 1998
  • 4[6]CRIEPI. Guide to lightning protection design of power stations, substations and underground transmission lines. CRIEPI Report No. 40, 1995.12
  • 5[8]EPRI. Transmission line reference book 345 kV and above second Edition . 1982
  • 6虞吴.现代防雷技术基础[M].北京:气象出版社,1994.
  • 7Anderson J G.345k V 及以上超高压输电线路.北京:电力工业出版社,1981.
  • 8Torres C R et al.Prediction of shielding failures on transmission lines.9th ISH 6815.
  • 9Jankov V.Distribution of the lightning strokes to the specific parts of transmission lines.9th ISH 6788.
  • 10谷定燮.500kV输变电工程设计中雷电过电压问题[J].高电压技术,2000,26(6):60-62. 被引量:65