期刊文献+

基于异步变频调制的UPS逆变数字锁相技术 被引量:2

Asynchronous Frequency-variable Modulation Algorithm based Digital Phase Lock Technique for UPS Inverter
下载PDF
导出
摘要 针对不间断电源(UninterruptedPowerSupply,UPS)控制的数字化趋势,提出了一种应用于数字化UPS的逆变锁相控制技术。与其它数字锁相技术不同的是,该技术基于一种可变频的异步调制算法。该算法具有精度高、程序实现简单、易于对逆变输出进行变频/移相控制等众多优点,再结合市电/逆变输出的相位反馈逻辑,即可实现UPS逆变与市电的同频同相输出。实验证明,该数字锁相技术不仅简单有效,而且锁相稳定、快速且锁相精度高,具有极高的实用价值。 This paper presents a digital phase lock technique for UPS inverter output control to meet the trend of UPS digital control.Unlike the other digital phase lock control,this technique is' based on a frequency-variable asynchronous modulation algorithm.The algorithm has many advantages such as easy program,high control precision, especially it can easily modify the inverter output phase and frequency.On the basis of this algorithm and combining phase detect logical,the inverter phase lock control can be realized.Finally,the experiment result has proved that the technique is not only simple but also effective, and the phase lock process is quick and stabile and has high lock precision.lt is of great practical value to UPS inverter control.
机构地区 湖南大学 创统科技
出处 《电力电子技术》 CSCD 北大核心 2006年第3期57-59,共3页 Power Electronics
基金 湖南省自然科学基金资助项目(03JJY5023)~~
关键词 不间断电源 逆变器 锁相环/异步调制 UPS inverter Phase Lock Loop (PLL)/Asynchronous Modulation
  • 相关文献

参考文献3

二级参考文献4

  • 1[1]Anolog Devices Inc.Adsp-2100 family user's manual.1994.
  • 2吴红缨,硕士学位论文,1995年
  • 3陈 坚编著.交流电机数学模型及调速系统[M]. 国防工业出版社, 1989
  • 4.Controllers Reference Guide Peripheral Library and Specific Devices[].TMSF DSP.1999