摘要
GW4-126系列接地刀闸在做型式试验中的动热稳定试验时,拍合式接地开关一般很难通过,采用升降式结构则能较顺利通过试验。究其原因,主要是电动力的方向引起的,因此,采用改变触指的通流方向的方法,可以解决这个问题。
When donig the dynamical thermal stability test of GW4-126 series grounding switch, the type of clap-close grounding switch is hard to pass the test, but using the rise and fall structure switch can pass successfully the test, the main reason is caused by the direction of the electrokinetic force, so solves the problem by changing the current flow direction of contact finger.
出处
《宁夏电力》
2006年第5期37-39,共3页
Ningxia Electric Power
关键词
隔离开关
接地开关
动热稳定试验
电压
电流
电动力
isolating switch
grounding switch
dynamical thermal stability test
voltage
current
electrokinetic force