提高低温空气源热泵性能的研究 被引量:8

Research on Improving the Performance of Air-source Heat Pump
下载PDF
导出
摘要 分析了热泵在低温环境工作时存在的问题。在热泵系统四通换向阀后的排气管上加旁通毛细管和在气液分离器中加过冷管。通过分析确定过冷管最小换热面积和旁通毛细管最佳长度范围。经实验证明在低温工况下时制热量提高显著。 The problems for heat pumps operating at low ambient temperatures were analyzed. A by- pass capillary tube was added on the discharge pipe behind the four- way valve and a tube was added in an accumulator in a heat pump system to solve the problem. The minimum heat transfer area of the tube for subcooling and the optimal length range of the by- pass capillary tube were determined. The experiment results show that heat output of the improved heat pump increased greatly at low ambient temperatures.
机构地区 哈尔滨商业大学
出处 《制冷学报》 CAS CSCD 北大核心 2007年第1期12-17,共6页 Journal of Refrigeration
关键词 热工学 空气源热泵 过冷回热 旁通毛细管 制热量 能效比 Pyrology Air- source heat pump Subcooled heat recovery By- pass capillary tube Heat output Energy efficiency ratio