期刊文献+

考虑母线分布电容影响的单端行波测距法 被引量:33

Single Ended Fault Location Approach Considering Bus Distributed Capacitance Effect
下载PDF
导出
摘要 分析了单端电压行波中各种可能存在的波头,得出了不考虑母线分布电容的方法不能完整地实现第2个反向行波识别的结论。推导了电压行波在分布电容处的传播特性,指出电压行波在分布电容处的初始反射系数恒为负。利用这个结论,提出了一种新型的第2个反向行波识别方法。理论分析和仿真结果表明,这种方法具有很高的可靠性,且不受线路两端母线类型的影响。 This paper analyzes possible surges in the single ended voltage traveling wave. Conclusion has been made that the approach without considering bus distributed capacitance can't accomplish the identification of the second reverse traveling wave accurately. That is, the promulgation characteristics of traveling wave at the shunt capacitor are deduced. Furthermore it is found that the initialized reflection coefficient of voltage traveling wave is always negative. With this conclusion, a new approach is proposed to identify the second reverse traveling wave. Theoretical analysis and simulation results show that the method proposed is of great reliability and applicability.
出处 《电力系统自动化》 EI CSCD 北大核心 2007年第2期70-73,共4页 Automation of Electric Power Systems
关键词 故障测距 输电线路 反向行波 母线分布电容 fault location transmission lines reverse traveling wave bus distributed capacitance
  • 相关文献

参考文献7

二级参考文献44

  • 1王志华,尹项根,张小波,黄雄,杨经超.利用CVT捕捉电压行波实现故障测距的分析与实践[J].电力系统自动化,2004,28(22):63-68. 被引量:29
  • 2葛耀中,徐丙垠,陈平.利用暂态行波测距的研究[J].西安交通大学学报,1995,29(3):70-75. 被引量:28
  • 3施慎行,董新洲,周双喜.单相接地故障行波分析[J].电力系统自动化,2005,29(23):29-32. 被引量:57
  • 4董新洲,葛耀中,徐丙垠,陈平,李京.利用GPS的输电线路行波故障测距研究[J].电力系统自动化,1996,20(12):37-40. 被引量:44
  • 5董新洲.小波理论应用于输电线路故障测距研究:博士学位论文[M].西安:西安交通大学,1996..
  • 6董新洲.小波理论应用于输电线路故障测距研究:[博士学位论文].西安:西安交通大学出版社,1996..
  • 7徐丙垠 葛耀中 等.利用暂态电流行波的输电线路故障测距技术.第五届全国继电保护学术会议论文集[M].北京:中国电机工程学会继电保护专委会,1993.125-132.
  • 8徐丙垠.利用暂态行波的输电线故障测距技术:博士学位论文[M].西安交通大学,1991..
  • 9陈平.利用暂态电流行波的输电线路故障测距装置的研制:硕士学位论文[M].西安交通大学,1994..
  • 10葛耀中,新型继电保护与故障测距的原理与技术,1996年