摘要
设计了一种基于多功能热管的高效吸附式制冰机组,采用氯化钙/活性炭复合吸附剂和氨作为吸附工质对。吸附床的加热解吸、冷却吸附及回热过程均由热管工作完成,对该新型吸附制冰机组进行了回质回热研究,结果表明,回质回热型循环可使机组的制冷性能系数COP提高25.5%,加热量减小约13%,同时冷却器负荷降低约21%;采用先回质后回热方式,在回质过程中继续加热解吸床可进一步增加机组制冰量。与传统回质相比,系统COP和单位质量吸附剂制冷功率SCP提高幅度均在15%以上,且机组SCP的提高幅度高于COP的幅度;吸附制冰机组性能随冷却水温度的升高而下降,但系统的SCP始终维持在较高的水平。当冷却水温度为27℃、蒸发温度为-18.9℃时,系统的SCP仍然高达356.5W.kg-1。
A multi-function heat pipe type adsorption ice maker, which uses activated carbon-CaCl2 as compound adsorbent and ammonia as refrigerant, was designed. For this test unit, the heating, cooling and heat recovery processes between two adsorbent beds were performed by multi-function heat pipes. The influence of recovery of mass and heat on the performance of adsorption ice maker was investigated. The experimental results showed improved recovery of mass and heat. The coefficient of performance (COP) was increased by 25.5 %, and the power consumption of boiler and the cooling capacity of cooler were reduced by about 13 % and 21 % respectively. When the mass recovery process was implemented before the heat recovery process, the mass recovery process with heating/cooling desorption/adsorption bed increased the rate of ice production obviously, which might help to increase COP and specific cooling power (SCP) by more than 15 % if compared with the conventional mass recovery process. The increase of SCP was higher than that of COP. Under the condition of different temperatures of cooling water, experiments showed that SCP was still high at a higher temperature of cooling water although the performance of adsorption ice maker dropped as temperature of cooling water became higher. At a cooling water temperature of 27℃ and an evaporating temperature of -18. 9℃, SCP was still as high as 356.5 W · kg
出处
《化工学报》
EI
CAS
CSCD
北大核心
2007年第5期1104-1109,共6页
CIESC Journal
基金
国家杰出青年科学基金项目(50225621)
上海市教委曙光跟踪计划项目(02GG03)~~
关键词
吸附制冷
复合吸附剂
回质
回热
热管
制冰机
adsorption refrigeration
compound adsorbent
mass recovery
heat recovery
heat pipe
ice maker