摘要
通过对两起国产12 kV铠装式金属封闭开关设备烧毁故障原因的分析和总结,指出目前运行的许多国产12 kV铠装式金属封闭开关设备存在结构性弱点,容易在天气骤变过程中出现凝露,发生绝缘闪络故障和扩大事故范围,并明确提出了解决对策和建议。同时建议制造企业和电力用户重视早期国产12 kV铠装式金属封闭开关设备的整改问题,以达到控制绝缘故障和杜绝“火烧连营”事故的发生。
This paper analyzed the fault reason of two domestic 12 kV metalclad switchgears' bum out, pointed out the structure shortcomings of domestic 12kV enclosed switchgears in service. Easy produce vapor condensation when weather sudden change, lead to insulation flashover fault and enlarge accident range. The countermeasures were proposed, and manufacture factory and power user were suggested to pay attention to rectification of switchgears in early stage, so as to control even eliminate insulation fault.
出处
《高压电器》
EI
CAS
CSCD
北大核心
2007年第3期232-234,236,共4页
High Voltage Apparatus
关键词
铠装柜
技术隐患
分析
对策
metalclad switchgear
technical potential problem
analysis
countermeasures