针对宝珠寺电站2号机3W定子接地保护动作的情况,对其原因进行了分析和查找,发现是由于PT柜内的A相二次保险接触不良造成的。通过更换二次保险的卡座后装置恢复正常运行。
The causes for 3W stator ground protection action are studied and looked for in No.2 unit at Baozhusi Hydropower Plant.It is found that this is caused by poor connection of A phase secondary safety device in PT block.The device operates normally after bayonet socket of the secondary safety device is changed.