期刊文献+

采用激光供能方法的光纤电流互感器 被引量:5

Optic-Fiber Current Transducer Powered with Laser Energy
下载PDF
导出
摘要 研制了一种新型的电流互感器,高压端采用Rogowski线圈作为电流传感头。传感头输出信号经A/D转换器变成数字量后编码成曼彻斯特码,由塑料光纤发送到低压端,用激光供能的方法为高压端的电子器件提供能源。低压端用D/A转换器恢复母线电流信号。该方法克服了传统电磁式电流互感器的固有缺点,也解决了直接从电力母线获得高压端电子器件工作能量的方法所带来的死区问题,加快了电子式电流互感器的实用化进程。 A novel current transducer which uses Rogowski core as current sensor head was designed. The signal from sensor head is sampled by a A/D converter, then the digital result is transformed to Manchester code and send to low voltage part by plastic fiber. Energy for electronic devices on the high voltage part is supplied with laser from low voltage part. At low voltage part, a D/A converter is used to resume the primary current signal. The design conquers the inherent defects of traditional electromagnetic current transducer, and resolves the problem of dead area in powering the electronic devices in high voltage part from the power line directly. The new current transducer will accelerate the practical process of electronic current transducer.
出处 《仪表技术与传感器》 CSCD 北大核心 2007年第5期5-6,17,共3页 Instrument Technique and Sensor
关键词 光供能 电流互感器 ROGOWSKI线圈 曼彻斯特码 laser energy supply current transducer Rogowski core Manchester code
  • 相关文献

参考文献8

二级参考文献25

  • 1李红斌,刘延冰,张卫军,李尔宁.用于110kV变电站的光学电流互感器[J].华中理工大学学报,1995,23(7):6-10. 被引量:17
  • 2易本顺,刘延冰,阮芳.多环光路结构光学电流传感头研究[J].传感技术学报,1996,9(4):39-42. 被引量:6
  • 3-.微机通信原理与实用技术[M].清华大学出版社,1998..
  • 4-.模数与数模转换技术[M].国防工业出版社,1990..
  • 5Oates C D M, Burnett A J, James C. The design of high performance Rogowski coils[C]. International Conference on Power Electronics, Machines and Drives. Bath, UK, 2002.
  • 6Ramboz J D. Machinable Rogwoski coil, design, and calibration[J].IEEE Trans on Instrumentation and Measurement, 1996, 45 (2) : 511-515.
  • 7Wang Haiming, Zheng Shengxuan. Methods for improving the measurement precision of the Rogowski coils[C]. Proceedings of 6th International Symposium on Test and Measurement. Vok 6. Dalian, China, 2005.
  • 8Rautiainen A, Helisto P, Mansten T, et al. 50 Hz current measurements with Rogowski coils[C]. Precision Electromagnetic Mesurements Conference Digest. Ottawa, Canada, 2002.
  • 9Ramboz J D. Machinable Rogowski coil, design and calibration[C]. Instrumentation and Measurement Tecnhology Conference. MA, USA,1995.
  • 10Liao Jingsheng, Guo Xiaohua, Luo Cheng, et al. Studies of Rogowski coll current transducer for low amplitude current (100 A) measurement[C]. Electrical and Computer Engineering, IEEE CCECE. Montreal,Canada, 2003.

共引文献91

同被引文献39

引证文献5

二级引证文献18

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部