摘要 针对新建机组运行数据有限无法及时获得数学模型的特点,对协调控制系统的常规控制策略进行优化和改进,形成了机炉全协调控制策略。应用此优化控制策略对1台新建200MW空冷机组和1台新建600MW超临界机组的协调控制逻辑进行组态和调试,在试运期间进行了负荷扰动试验和电网AGC试验。运行实践表明,协调控制系统设计合理,适合机组运行特性,能够满足机组运行和电网的要求,为把新建大型火电机组纳入电网AGC控制提供借鉴。 Considering that timely mathematic model could not be obtained because of limited operating data for the newly built generating unit, flail-coordinated control policy is set up after the optimization and improvement of conventional control policy for the coordinated control system. This optimized control policy is applied to the configuration and commissioning of coordinated control logic for a newly built 200 MW air-cooled generating unit and a 600 MW supercritical generating unit. Load disturbance test and AGC test were carried out during test operation. The operation shows the design of the coordinated control is reasonable, and fit to the operating characteristics and meets operation of the generating unit and the demand of power system, thus references for newly built large-scale generating unit to be adapted to AGC control is provided.
出处 《东北电力技术》 2007年第8期1-4,共4页 Northeast Electric Power Technology
关键词 直吹式锅炉 常规控制 协调控制系统 控制策略 优化 Direct-firing boiler Conventional control Coordinated control system Control policy Optimization
  • 相关文献

参考文献4

二级参考文献16

  • 1柏建国,吕炳朝.多模态PID控制器[J].仪器仪表学报,1993,14(1):26-32. 被引量:23
  • 2Shen Jiong,1991年
  • 3Wu Weiyong,1991年
  • 4张化光,1991年
  • 5Feng W,1989年
  • 6胡克定,东南大学学报,1989年,19卷,1期,69页
  • 7张文龙,中国电机工程学报,1985年,5卷,3期,10页
  • 8刘向杰,模糊控制器的算法结构分析及其在电厂锅炉控制中的应用研究 [D],1997年
  • 9Zhang Guijun,Proc 3 5thIEEECDC,1996年,2527页
  • 10董苏云.浅谈初中数学教学中学生观察能力的培养[J].学周刊(上旬),2013(3):56-57. 被引量:4

共引文献148

同被引文献66

引证文献17

二级引证文献64

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部