期刊文献+

基于分形测度的电压暂降持续时间检测 被引量:9

Voltage Sag Duration Detecting Method Based on Fractal Number Measurement
下载PDF
导出
摘要 基于分形技术,提出了一种新型的电压暂降持续时间检测方法。该方法利用分形数计算信号波形的平滑度,识别暂降起止时刻的高频暂态振荡,然后将实时计算的分形数与阈值进行比较,得到起止时间的定位进而求得持续时间。基于PSCAD/EMTDC软件进行故障暂态仿真,在有无谐波畸变的情况下分别进行测试,证明该方法有效可行。同时进一步将此方法与小波变换及有效值法分析比较,表明其具有较好的实时性和准确性。  Based on fractal technology,a novel voltage sag duration detecting method is proposed. This method calculates the fractal number of signal waveform as an evenness index which is used to detect the high frequency transient oscillation arising at the start and stop time of voltage sag. Then the fractal number is refined through threshold comparison method to accurately reflect the signal dynamics and find the duration of sag event. A fault model was simulated using PSCAD/EMTDC software. The sag waveforms with and without harmonics were detected respectively to verify the feasibility of the proposed method. This method is further compared with wavelet transform and root mean square(RMS)method. The results show its good performance on rapidity and accuracy.
出处 《电工技术学报》 EI CSCD 北大核心 2007年第9期148-153,共6页 Transactions of China Electrotechnical Society
基金 国家自然科学基金重点资助项目(50437010) 浙江大学-日本富士电机联合研究资助项目。
关键词 电力系统 电能质量 电压暂降 持续时间 分形测度 Power system,power quality,voltage sag,duration,fractal number measurement
  • 相关文献

参考文献13

  • 1Wang B,Xu W,Pan Z C.Voltage sag state estimation for power distribution systems[J].IEEE Transaction on Power Systems,2005,20 (2):806-812.
  • 2IEEE standards coordinating committee 22 on power quality.IEEE Recommended Practice for Monitoring Electric Power Quality[S].
  • 3ITI (CBEMA) Curve Application Note.[Online].Available:http://www.itic.org/archives/iticurv.pdf
  • 4Wang J,Chen S,Lie T T.System voltage sag performance estimation[J].IEEE Transaction on Power Delivery,2005,20 (2):1738-1747.
  • 5刘应梅,白晓民,王文平,易俗.基于Dyn测度的电压暂降检测方法[J].电力系统自动化,2004,28(2):45-49. 被引量:17
  • 6杨亚飞,颜湘武,娄尧林.一种新的电压骤降特征量检测方法[J].电力系统自动化,2004,28(2):41-44. 被引量:83
  • 7Poisson O,Rioual P,Meunier M.Detection and measurement of power quality disturbances using wavelet transform[J].IEEE Transaction on Power Delivery,2000,15 (3):1039-1044.
  • 8周文晖,李青,周兆经.采用小波多分辨率信号分解的电能质量检测[J].电工技术学报,2001,16(6):81-84. 被引量:57
  • 9王克星,宋政湘,陈德桂,王建华,耿英三.基于小波变换的配电网电压暂降的干扰源辨识[J].中国电机工程学报,2003,23(6):29-34. 被引量:86
  • 10Umeh K C,Mohamed A,Mohamed R,et al.Characterizing nonlinear load harmonics using fractal analysis[C].Proceedings of the 2004 International Symposium on Circuits and Systems,2004,5:932-935.

二级参考文献22

  • 1张济中.分形[M].北京:清华大学出版社,1995..
  • 2Chan K Kara A.动态电压恢复装置及其特性(Dynamic Voltage Restorer and Its Performance)[J].国际电力(lnternational Electric Power for China),1998,(1):49-51.
  • 3韩英铎 严干贵 姜齐荣 等(Han Yingduo Yan Gangui Jiang Qirong et al):.信息电力与FACTSampDFACTS技术(Information Power and FACTSampDFACTS)[J].电力系统自动化(Automation of Electric Power Systems),2000,24(19).
  • 4The Working Group on Monitoring Electric Power Quality. Recommended practice for monitoring electric power quality [S]. IEEE Std 1159-1995.
  • 5Mark E McGranaghan, David R Mueller. Voltage sags in industrial systems [J]. IEEE Transactions on Industry Applications, 1993,29(2): 397-403.
  • 6Christopher J Melhorn, Timothy D Davis, George E Beam. Voltage sags: their impact on the utility and industrial customers [J]. IEEE Traus on Industry Applicatious, 1998, 34(3): 549-558.
  • 7Campbell A, McHattie R. Backfilling the sinewave--a dynamic voltage restorer case study [J]. Power Engineering Journal, 1999,13(3): 153-158.
  • 8Buxton R. Protection from voltage dips with the dynamic voltage restorer [C]. IEE Half Day Colloquium, London, 1998.
  • 9Bollen M H J. Voltage sags in three-phase systems [J]. IEEE Power Engineering Review, September 2001: 8-11.
  • 10Stefano Quaia, Fabio Tosato, Roberto Visintini. Mitigation of voltage sag effects on sensitive plants: an examplary case study [J]. Electric Power Systems Research, 2002, 61: 93-99.