期刊文献+

有风条件下自然排烟准稳态的双区模型分析 被引量:5

Study of Quasi-Steady State of Natural Smoke Exhaust Under Surrounding Winds Using a Two-Layer Zone Model
下载PDF
导出
摘要 采用双区模拟思想对有风条件下自然补气、自然排烟过程准稳态进行了分析.定义了"总风压系数"用以评价外界环境风对自然排烟过程的影响程度,并对不同条件下的自然排烟准稳态进行了计算讨论,给出了不同总风压系数下自然排烟临界失效风速的计算表达式.结果表明:总风压系数非负时,外界风的存在提高了自然排烟的效率,其影响程度与风速、火源功率、排烟口面积有关;总风压系数为负时,外界风的存在降低了自然排烟的效率,但只要外界风速不超过临界失效风速,自然排烟就是有效的,其准稳态时的烟层界面高度要低于无风时的烟层界面高度.因此,在启动建筑自然排烟系统时,应对补气口、排烟口位置进行选择,尽量使总风压系数为正,以提高排烟效率. Quasi-steady state of natural smoke exhaust with natural air makeup under surrounding winds was studied using a simple two-layer zone model. A "total pressure coefficient" was proposed to assess the significance of wind on natural smoke exhaust. Quasi-steady states under different conditions and critical invalidating velocities of wind for natural smoke exhaust were calculated. The results show that when the pressure coefficient is positive, the surrounding wind will enhance the performance of smoke exhaust, and the extent of enhancement depends on wind velocity, fire power, vent area and so on. When the pressure coefficient is negative, natural smoke exhaust will work until the wind velocity is bigger than the critical invalidating velocity. When operating a natural smoke exhaust system of a building under surrounding wind, the positions of vents and air inlets should be chosen to make the total pressure coefficient positive, so as to make the wind strengthen the extraction.
出处 《中国矿业大学学报》 EI CAS CSCD 北大核心 2007年第6期728-733,共6页 Journal of China University of Mining & Technology
基金 国家"十五"科技攻关计划项目(2001BA803B04)
关键词 自然排烟 双区模型 环境风 准稳态 总风压系数 natural smoke exhaust two-layer zone model surrounding wind quasi-steady state total pressure coefficient
  • 相关文献

参考文献9

  • 1NFPA 204,Standard for smoke and heat venting[S].National Fire Protection Association,2002.
  • 2COOPER L Y.Combined buoyancy-and pressure-driven flow through a shallow,Horizontal Circular Vent[J].Journal of Heat Transfer,1995,117:659-670.
  • 3POREH M,TREBUKOV S.Wind effect on smoke motion in building[J].Fire Safety Journal,2000,35:257-273.
  • 4CHOW W K,LI J.Wind effects on performance of static smoke exhaust systems:horizontal ceiling vents[J].ASHRAE Transactions,2004,110:479-488.
  • 5倪天晓.剧院建筑火灾烟气流动与控制的数值模拟研究[D].长沙:中南大学土木建筑学院,2006.
  • 6QUINTIERE J Q.Fundamentals of enclosure fire "zone model"[J].Journal of Fire Protection Engineering,1989,1:99-119.
  • 7NFPA 92B,Guide for smoke management systems in malls,atria,and large areas[S].National Fire Protection Association,2000.
  • 8MACDONALD A J.Wind loading on buildings[M].New York:Wiley,1975.
  • 9ZUKOSKI E E,KUBOTA T,CETEGEN B.Entrainment in fire plumes[J].Fire Safety Journal,1981,3:107-121.

共引文献1

同被引文献46

  • 1王国栋,霍然,易亮,周允基.热烟测试用于评价建筑烟控系统的讨论[J].消防科学与技术,2005,24(1):25-27. 被引量:16
  • 2胡浩,聂磊,李玉臻.国家博物馆大广场中庭烟气控制研究[J].消防科学与技术,2006,25(1):47-49. 被引量:5
  • 3高俊霞,史聪灵,钟茂华,符泰然.地铁高架车站站厅火灾烟气流动与控制[J].中国安全生产科学技术,2007,3(2):49-54. 被引量:7
  • 4Cooper L Y. Combined buoyancy-and pressure-driven flow through a shallow, horizontal circular vent[J]. Journal of Heat Transfer, 1995, 117 : 659 - 670.
  • 5Porch M, Trebukov S. Wind effect on smoke motion in building[J]. Fire Safety Journal, 2000, 35:257 -273.
  • 6Chow W K, Li J. Wind effects on performance of static smoke exhaust systems: horizontal ceiling vents[J]. ASHRAE Transactions, 2004, 110 : 479 - 488.
  • 7Standard for Smoke and Heat Venting[S]. NFPA 204, 2002.
  • 8民用建筑防排烟技术规程[S].DGJ08-1988-2000,2000.
  • 9Quintiere J G. Scaling applications in fire research[J]. Fire Safety Journal, 1959, 15( 1 ) :1 - 12.
  • 10Macdonald A J. Wind loading on buildings[M]. New York: Wiley, 1975.

引证文献5

二级引证文献31

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部