摘要
在电能计量互感器出现断相故障的理论分析基础上,应用Matlab/Simulink构建了某35kV高压三相三线电能计量的仿真模型,并对电能计量互感器正常运行和多种不同断相故障现象进行了仿真,与实测数据和理论结果比较,验证了仿真模型的正确性,从而应用该模型对实际电能计量出现异常数据的现象进行了故障仿真分析,有效地辅助解决了实际工程问题。
Based on the theoretical analysis of the inductor of electric energy measurement under the faults of break phase, models of a three-phase three-line inductor of electric energy measurements in a practical 35kV high voltage power system were established by using Matlab/Simulink. The performances of the inductor of electric energy measurement under both the normal operation and different faults of the break phase were simulated and analyzed. The proposed models were demonstrated by comparison with the measuring data and the theoretical analysis. Applying to the models, the abnormal data of a factual inductor of electric energy measurement was proposed and judged perfectly by fault simulation, which was helpful to solve the practical engineering problems.
出处
《系统仿真学报》
EI
CAS
CSCD
北大核心
2008年第11期3055-3058,共4页
Journal of System Simulation
关键词
电力系统
电能计量
互感器
异常断相
故障仿真
power system
electric energy measurement
inductor
abnormal break phase
fault simulation