期刊文献+

岩滩水电站3号机组转轮改造的实践与探讨 被引量:2

Practice and Discussion of Runner Improvement for No.3 Unit in Yantan Hydropower Station
下载PDF
导出
摘要 针对岩滩水电站3号机组的振动与转轮裂纹问题,作者进行了相关的分析与探讨。发现是由于高水头部分负荷区压力脉动等4个原因引起厂房振动,由于制造过程中的缺陷等原因造成转轮裂纹。通过采取转轮的更新改造及泄水锥气水分离等措施后,机组振动及转轮裂纹问题得以解决。 Problems of vibration and runner crack of No. 3 unit in Yantan hydropower station are analyzed. It is founded that the vibration of workshop is caused by four reasons, such as pressure fluctuation of high water head load, and runner crack is caused by the manufacture defect. Several measures are taken to solve these problems, such as the improvement of runner and air-water separation of runner cone.
作者 宋自灵 吴武
出处 《广西电力》 2008年第5期6-9,14,共5页 Guangxi Electric Power
关键词 混流式水轮机 振动 脉动 裂纹处理 francis turbines vibration fluctuation crack treatment