摘要 预制式电缆终端在现场安装时,存在应力锥安装错位的情况。为此,运用有限元法研究电缆终端应力锥安装错位时的高压静电场的分布和数值大小,得出结论:当应力锥覆盖电缆半导电层不满60mm时,电场畸变较小,对设备危害不大;当应力锥覆盖电缆半导电层超过60mm时,电场畸变大,易发生局部放电。现场试验结果与该结论相符。 The stress cone of prefabricated cable terminal may be installed incorrectly on site. Therefore, the distribution and magnitude of HV electrostatic field in incorrectly installed stress cone of cable terminal are studied by use of finite element method. It is concluded that when the stress cone coverage on the semi-conductive layer of cable is less than 60 mm, smaller field distortion is caused and the impact on equipment is not great; when the stress cone coverage on the semi-conductive layer of cable exceeds 60 mm, the filed distortion is large and partial discharge may be caused easily. Field test results correspond with the conclusion.
出处 《广东电力》 2009年第2期25-27,37,共4页 Guangdong Electric Power
关键词 有限元 电缆终端 静电场 应力锥 安装错位 finite element cable terminal electrostatic field stress cone incorrect installation
  • 相关文献

参考文献13

二级参考文献25

  • 1陈守直,祝丽雯,罗俊华,袁淳智.电缆附件电场有限元计算方法[J].高电压技术,1996,22(3):14-15. 被引量:14
  • 2刘其昶.电气绝缘结构设计原理(中)[M].西安:西安交通大学出版社,1987..
  • 3[4]G.P.Van der wijk,等.Development and qualification of a new 400 kV XLPE cable system with integrated sensors for diagnostics[C].CIGRE 1998,21~103.
  • 4[5]J.L.Parpal,等.Prequalification testing of 345 kV extruded insulation cable system[C].CIGRE 1998,21~101.
  • 5户谷敦,等.275 kVCVケ一ブル用新型接续部の开发[J].电气现场技术,1997,(10):32-37.
  • 6[7]J.Oesterheld,等.Optimized design of accessories for245 kV and 420 kV XLPE cables[C].CIGRE 1992,21~202.
  • 7[10]应启良.参加1998年IEC TC20、SC20A、SC20B及SC20C会议技术总结报告[R].上海:上海电缆研究所,1998.
  • 8[11]H.Schadlich,等.Field testing of XLPE-insulated cables in 220 kV and 380 kV systems[C].CIGRE1990,21~106.
  • 9[12]K.Kikuchi,等.Recent technical progress in accessories for extra high voltage XLPE cables in Japan[C].CIGRE 1992,21~203.
  • 10[13]Kazushi Kobashi,等.Prefabricated joints for 275 kV XLPE cables[J].Furukawa Review,1994,13:51~61.