形变台站防雷保护及接地改进 被引量:8

Protection and Grounding Against Lightning in the Deformation Seismostation
下载PDF
导出
摘要 通过对典型形变台站遭雷害的调查,指出形变台站受雷害或干扰的途径是:(1)雷击避雷针的雷电过电压和大电流;(2)交流供电线路上的雷直击过电压与感应过电压等。在分析和归纳后针对性地提出并实践了:(1)应用半导体少长针消雷器防直击雷害;(2)建立接地地网和设计过压保护单元电路或雷击期启用UPS以防电子设备的感应雷害;(3)对架空供电进线换用埋地金属外皮屏蔽电缆以防线路来波侵入等综合治理措施,收到了显著的社会和经济效益。 Through investigation on the typical deformation seismostation which are damaged by lightning, two ways of lightning damage are pointed out in the paper:(1) The overvoltage and large current formed when lightning strikes lightning rod; (2) The overvolotage of supply power lines formed in the direct hits or induction of lightning. After analysis and summary, the measures are presented and applied as follows:(1) Establishing the semiconductor lightning eliminator to prevent the direct lightning; (2) Improving grounding mesh and adding overvolotage protection circuits or supplying power by UPS in process of lightning; (3) Changing overhead supply power lines into power cables with metal shield buried in ground. It has been proved that the measures are very effective.
出处 《中国地震》 CSCD 北大核心 1998年第1期81-89,共9页 Earthquake Research in China
关键词 变形台站 地震台 防护措施 雷电 防雷 接地改进 Deformation seismostation, Preventive measures, Thunder hazard
  • 相关文献

参考文献5

  • 1陈德福,地震地形变观测技术,1995年
  • 2陈德福,地壳形变动力学观测与研究,1993年
  • 3程世国,避雷装置检测技术手册,1991年
  • 4应洪正,雷电与静电,1985年,2期
  • 5解广润,电力系统过电压,1985年