以单位冷量空调总能耗为目标函数,对大温差空调冷冻水系统方案进行了优化计算,得出了空调冷冻水系统最佳供回水温差为7.2℃,探讨了大温差空调水系统方案的适用场合。
In this paper, the author optimizes calculation for air-conditioning chilled water system with largest temperature difference, with the unit of total energy consumption quantity of air-conditioning system for target function. He puts forward the best temperature difference for energy-efficient is 7.2 ℃, and discusses which is the appropriate occasion for system project with largest temperature difference.
出处
《山西能源与节能》
2009年第6期77-79,共3页
Shanxi Energy and Conservation
关键词
大温差
空调系统
能耗
节能
largest temperature difference
air-conditioning system
energy consumption
energy saving