导出
摘要 推导了煤矿井下低压电网不同位置发生单相漏电时的零序电流计算公式,用电流相量的实部和虚部比较了各零序电流的幅值关系与相位关系,并提出了一种新的选择性漏电保护方案。通过Matlab仿真与快速傅里叶变换(FFT,Fast Fourier Transform)对该方案进行了验证。结果表明,此方法不仅可以实现漏电保护的横向、纵向选择性,而且无需采集零序电压,既提高了漏电保护的可靠性,又降低了硬件成本。 Deduced zero-sequence current formulae when single-phase earth leakage happened in underground low voltage distribution networks' different places,compared zero-sequence current amplitude relationships and phase relationships with current phasor's real part and imaginary part,and proposed a new selective earth leakage protection scheme.The scheme was verified by simulation via Matlab and calculation via Fast Fourier Transform.The results indicate that this method achieves lateral and longitudinal selectivity,avoids zero-sequence voltage's collection,enhances protection reliability,and cuts hardware's cost.
出处 《煤炭学报》 EI CAS CSCD 北大核心 2010年第3期515-519,共5页 Journal of China Coal Society
关键词 零序电流 群体比幅比相 漏电保护 低压电网 快速傅里叶变换(FFT) zero-sequence current amplitude and phase comparison earth leakage protection low voltage distribution networks Fast Fourier Transform(FFT)
  • 相关文献

参考文献15

  • 1高彦,王念彬,王彦文.基于零序功率方向选择性漏电保护系统的研究[J].煤炭科学技术,2005,33(11):43-45. 被引量:32
  • 2张长森,柯熙政.矿井低压电网漏电保护的现状及发展趋势[J].煤矿机电,2005,26(5):73-77. 被引量:19
  • 3廖文.基于面保护原理的小电流接地选线装置[J].电工技术,2007(5):37-38. 被引量:1
  • 4Xing Yahui,Lu Yanping,Zhao Jun. Selecting the faulty line through correlation of zero-sequence currents in non-solid earthed network [ A]. 2009 Asia-Pacific Power and Energy Engineering Conference [ C ]. Piscataway, N J, USA : IEEE,2009 : 1 - 4.
  • 5Kang Xiaoning, Jiale Suonan, Bo Zhiqian. Parameter identification algorithm for faalt location based on distributed transmission line model[ A]. IEEE Power and Energy Society 2008 General Meeting [ C ]. Piscataway, N J, USA : IEEE, 2008 : 1 - 7.
  • 6Jung C K,Lee J B, Wang X H, et al. Wavelet based noise cancellation technique for fault location on underground power cables [ J ]. Electric Power Systems Research,2007,77(10) :1 349 - 1 362.
  • 7Kim Chulhwan, Kim Hyun, Ko Younghun, et al. A novel fault-detection technique of high-impedance arcing faults in transmission lines using the wavelet transform[J]. IEEE Transactions on Power Delivery,2002,10 (4) :921 -929.
  • 8Wiktor Charytoniuk, Lee Weijen, Chen Moshing, et al. Arcing fault detection in underground distribution networks-feasibility study[ J]. IEEE Transactions on Industry Applications ,2000,36 (6) :1 756 - 1 761.
  • 9Lin Xiangning, Zhao Zhimin, Bo Zhiqian. An adaptive inverse time- delay characteristic of the zero-sequence overvoltage protection for identification of the single-phase earth fault in the neutral non-effec- tively grounded power systems [A]. 2009 IEEE Power and Energy Society General Meeting [ C ]. Piscataway, N J, USA : IEEE,2009 : 1 - 5.
  • 10Nam Soonryul,Sohn Jinman, Kang Sanghee, et al. Ground-fauh location algorithm for ungrounded radial distribution systems [J].Electrical Engineering,2007,89 (6) :503 - 508.