期刊文献+

基于模型识别的三相重合闸永久性故障判别 被引量:14

Discrimination of Permanent Faults for Three-phase Autoreclosing Based on Model Identification
下载PDF
导出
摘要 提出一种基于模型识别的带并联电抗器输电线路三相重合闸永久性故障判别方法。该方法以选相结果为基础,以瞬时性故障π形模型为识别模型,将并联电抗器电流作为已知量,求取本端及对端线模电压和电容电流的线模分量,进而求解两端并联电抗器电流和电容电流线模分量之和。瞬时性故障时,故障模型与识别模型一致,求解值等于0;永久性故障时,故障模型与识别模型不一致,求解值不等于0。据此可以判别是否为永久性故障。电磁暂态分析程序(EMTP)仿真表明,该方法能够有效识别永久性故障,可靠实现带并联电抗器输电线路的三相自适应重合闸。 A novel permanent fault discrimination method for three-phase auto-reclosing of transmission lines with shunt reactors is proposed. The method takes phase selection results as basis and considers the transient fault model as the reference. It takes currents of shunt reactors as known quantities and calculates the aerial modal component of capacitive currents and voltages of both terminals. The formula is further established for summing the currents of shunt reactors and aerial modal component of capacitive currents of both terminals. In case of a transient fault,the result of the formula is zero because the actual fault model is consistent with the reference. But in case of a permanent fault,the result of the formula is non-zero because the actual fault model is inconsistent with the reference. EMTP simulation results show that the proposed method can reliably and effectively distinguish permanent faults from transient faults and apply to three-phase adaptive reclosure scheme on transmission lines with shunt reactors.
出处 《电力系统自动化》 EI CSCD 北大核心 2010年第8期81-85,共5页 Automation of Electric Power Systems
基金 国家自然科学基金资助项目(50877062)~~
关键词 模型识别 线模分量 输电线路 并联电抗器 三相自适应重合闸 电力系统 model identification aerial modal component transmission line shunt reactors three-phase adaptive reclosure power systems
  • 相关文献

参考文献11

二级参考文献98

共引文献210

同被引文献158

引证文献14

二级引证文献135

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部