期刊文献+

浅析前湾燃气轮发电机继电保护配置及运行情况 被引量:8

Study on relay protection and its operational performance of Qianwan gas turbine generator
下载PDF
导出
摘要 介绍了燃气轮发电机电气部分的特殊性,阐述了燃气机组特有的静止变频器的工作原理及保护配置,分析了专为机组变频启动所配置的低频过流和启停机保护的设计思想,并介绍了在机组运行的不同阶段,发电机保护的投退情况。对发电机机端电压互感器谐振、SFC故障、励磁系统参数不匹配等曾经引起机组启动失败的案例进行了分析和总结,提出一些解决方法,介绍了检修经验,提高了燃机电厂的电气检修水平。 This paper introduces the special electric part of gas turbine generator at first and presents the operational principle of SFC and its relay protection configuration.Then it analyses the design philosophy of low frequency over current and starting up protection relay.It also lists the different relays using time on various stage of generator running.At last,it focuses on the operational performance and ever-happened typical faults of gas turbine generator,such as PT resonance oscillation,SFC fault,parameter of field system not matching,etc.It puts forward some suitable measures and maintenance experiences,so as to improve the maintenance quality of gas turbine power plant.
作者 王文志 余芳
出处 《电力系统保护与控制》 EI CSCD 北大核心 2010年第11期130-132,共3页 Power System Protection and Control
关键词 燃气轮发电机 静止变频器 出口断路器 保护配置 发电机保护 gas turbine generator static frequency converter GCB protection configuration relay protection of generator
  • 相关文献

参考文献3

二级参考文献6

共引文献17

同被引文献31

引证文献8

二级引证文献18

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部