期刊文献+

采用动态相量法的电压闪变检测 被引量:2

Flicker Detection Using Dynamic Phasors Method
原文传递
导出
摘要 数字式闪变仪多采用均方根(RMS)值作为输入,经傅立叶变换得到电压波动频率和幅值,再通过查表的方式直接计算出瞬时闪变视感度。然而以上过程多采用数值计算,缺乏准确的解析表达式。为此采用了动态相量法,对单一频率的正弦调制工频电压进行分析,得到RMS电压频谱的解析表达式,并由此计算得到一组新的使得瞬时闪变视感度为1的频率与RMS电压波动对照表,分析表明,随着频率的增加,其结果与调幅波电压波动差距较大,因此宜采用基于RMS的新的对照表,以正确计算闪变值。最后将以上分析扩展到多调幅波频率的情况,结论一致。 The digital flicker meter often calculated the frequencies and amplitudes of voltage fluctuation by Fourier transform dealing with the RMS values of a voltage waveform and then calculates the instantaneous flicker sensation level directly by checking table.Yet the above process was usually completed by numerical calculation,lack of accurate analytical expression.So dynamic phasor approach was adopted to calculate the analytical expression of the RMS values spectrum of power frequency voltage modulated by single frequency sinusoidal wave,and a new comparison table on frequencies and corresponding voltage fluctuations of RMS,which make instantaneous flicker sensation level to be one,is obtained.The analysis show that the voltage fluctuations of RMS values are quite different from those of modulation wave with the increase of frequency.The new comparison table based on RMS values should be adopted to calculate flicker value correctly.Finally,consistent conclusions can be drawn when the above analysis is extended to multiple modulation wave frequencies.
出处 《高电压技术》 EI CAS CSCD 北大核心 2010年第5期1293-1298,共6页 High Voltage Engineering
基金 国家自然科学基金(50747043) 福建省科技计划重点项目(2007H0022)~~
关键词 电压闪变 频率特性 动态相量 电能质量 信号处理 检测 voltage flicker frequency characteristics dynamic phasors power quality signal process detection
  • 相关文献

参考文献30

二级参考文献191

共引文献272

同被引文献28

  • 1杨坤,杨洪耕.基于小波测位的闪变检测算法及其实现[J].继电器,2004,32(21):48-51. 被引量:8
  • 2何瑞文,蔡泽祥.结合谐波特征的可控串补动态相量法建模与特性分析[J].中国电机工程学报,2005,25(5):28-32. 被引量:21
  • 3肖湘宁.电能质量分析与控制[M]北京:中国电力出版社,2004.
  • 4Renner H,Sakulin M. Flicker propagation in meshed high voltage networks[A].Orlando,Florida,2000.1023-1028.
  • 5Yang X,Papic I. Study of flicker propagation in electric grid by modeling and on-site flicker measurements[A].Minneapolis,MN,2010.1-5.
  • 6孙树勤.电压波动与闪变[M]北京:中国电力出版社,1998.
  • 7Alt X,Salor O,Cadirci I. A new flicker contribution tracing method based on individual reactive current components of multiple EAFs at PCC[J].IEEE Transactions on Industry Applications,2010,(05):1746-1754.
  • 8SHAO Zhen-guo. Tracking the impedance of fluctuant load using wavelet transform[A].2008.1603-1607.
  • 9Stanko vic A M,Sanders S R. Dynamic phasors in modeling and analysis of unbalanced polyphase AC machines[J].IEEE Transactions on Energy Conversion,2002,(01):107-113.doi:10.1109/60.986446.
  • 10鄂志君,应迪生,陈家荣,张明,房大中.动态相量法在电力系统仿真中的应用[J].中国电机工程学报,2008,28(31):42-47. 被引量:25

引证文献2

二级引证文献8

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部