摘要 对NH_3/CO_2复叠式制冷系统进行了性能实验,并对NH_3/CO_2复叠系统、两级NH_3系统以及单级NH_3系统的性能进行了比较。结果表明,当CO_2冷凝温度升高时,复叠系统的COP先增大后降低;随着冷凝蒸发器中换热温差的降低、CO_2蒸发温度的升高,系统COP逐渐升高。在较低的蒸发温度下,NH_3/CO_2复叠系统的COP高于两级NH_2、单级NH_2系统。结果表明自然工质的NH_3/CO_2复叠式制冷系统在低温工况下具有良好的应用前景。 In order to investigate the performance of NH3/CO2 cascade refrigeration system, an experiment was conducted. Its performance was compared with the performance of two stage NH3 cycle and single NH3 cycle. The result presents that there is an optimum COP for the cascade system as the CO2 condensing temperature increases and that the system COP goes up with a decrease in temperature difference of the cascade condenser or an increase in CO2 evaporating temperature; the performance of NH3/CO2 cascade cycle is superior to that of two stage NH3 cycle and single NH3 cycle. NH3/CO2 cascade refrigeration system is suitable for the low temperature application.
出处 《冷藏技术》 2010年第2期9-12,共4页 Journal of Refrigeration Technology
关键词 热工学 性能 系统实验 NH3/CO2复叠式制冷 螺杆压缩机 Pyrology Performance System experiment NH3/CO2 cascade refrigeration Screw compressor
  • 相关文献

参考文献7

  • 1金嘉玮,叶尉南,杨一凡.CO_2/NH_3复叠式制冷系统在美国大型冷库的应用实例[J].冷藏技术,2007,30(2):1-9. 被引量:16
  • 2Getu H M, Bansal P K. Thermodynamic analysis of an R744-R717 cascade refrigeration system. Int. J. Refrigeration, 2007.31 (1) :45-54.
  • 3Lee T S, Liu C H, Chen T W. Thermodynamic analysis of optimal condensing temperature of cascade- condenser inCOJNH3 cascade refrigeration systems. Int. J. Refrigeration, 2006. 29 (7): 1100-1108.
  • 4Ferkndez-seara J, Arias A, Dopazo A, et al. Simulation model of a CO2/NH3 cascade refrigeration system prototype. International Congress of Refrigeration, Beijing, 2007.
  • 5Sawalha S, Cabrejas C.P, Likitthammanit M, et al. Experimental investigation of NH3/CO2 cascade system and comparison to R404A system for supermarket. International Congress of Refrigeration, Beijing, 2007.
  • 6查世彤,马一太,王景刚,魏东.CO_2-NH_3低温复叠式制冷循环的热力学分析与比较[J].制冷学报,2002,23(2):15-19. 被引量:34
  • 7顾兆林,刘红娟,李云.NH_3/CO_2低温制冷系统研究[J].西安交通大学学报,2002,36(5):526-540. 被引量:21

二级参考文献10

  • 1王景刚,马一太,魏东,王侃宏.CO_2跨临界双级压缩带膨胀机制冷循环研究[J].制冷学报,2001,22(2):6-11. 被引量:34
  • 2W.R. Kitzmiller. Advantages of CO2 - Ammonia system for low - temperature refrigeration. Power, 92 - 94, January, 1932.
  • 3J. PettersenA., A, Jakobsen. A dry ice slurry system for low temperature refrigeration. International symposium on refrigera tion in sea transport today and in the future. Gdansk, Poland, Sep/Oct, 1994.
  • 4G. Lorentzen. Revival of carbon dioxide as a refrigerant. Int. J.Refrig, 17(5) :292 - 301,1994.
  • 5MM REFRIGERATION. CO2 - Ammonia cascade systems 2007.04.
  • 6胡姆.格贝哈尔特Nesde公司采用NH3和CO2制冷剂-采用天然制冷剂替代R1381的一个大型冷库[J].制冷与空调技术,2002,1:46-52.
  • 7NestleUK.Croydon 尹从绪翻译.surry“大型冻干工厂中CO2/NH3制冷系统替代R22制冷系统应用实例”[J].中国制冷简报,2007,.
  • 8王如竹主编.“制冷学科进展研究与发展报告”中杨昭第一章制冷空调新工质与自然冷媒中1-1制冷剂历史1-4-3自然工质中有关章节.
  • 9Heinz. Jackmann. HansGuntnerC, mbh. Furstenfeldbruck, Bavaria, Germany. "Air coolers, Air currents and Temperature Distribution in Large Refrigerated Warehouses" 2007 IIAR Technical paper 5 # .
  • 10林高平,顾兆林.跨临界 CO_2 制冷循环性能的研究[J].西安交通大学学报,1998,32(8):35-38. 被引量:13