期刊文献+

数字化变电站系统可靠性与可用性研究 被引量:62

Reliability and availability study of the digital substation system
下载PDF
导出
摘要 基于IEC 61850的数字化变电站系统具有传统变电站系统所不同的结构与特点。现有的变电站可靠性分析方法多针对单装置或单间隔,鲜有针对整个变电站自动化系统。介绍了基于IEC 61850的数字化变电站系统的典型结构,分析了提高数字化变电站可靠性的主要方法,提出一种计算全站可靠性的方法。该方法将数字化变电站系统划分为通信系统、控制系统、保护系统以及站控层系统。利用可用性框图,分别计算每个子系统可靠性参数,然后通过系统可用性框图,计算出整个变电站的可靠性参数。利用该方法对一典型数字化变电站系统的可靠性进行了分析计算。结果表明,在合理采用装置冗余并采用基于IEC 62439-PRP的并行网络冗余后,数字化变电站系统的可靠性能够满足IEC 61508的要求。 The digital substation system based on IEC 61850 is different from the conventional substation system in the architecture and the characteristics.While the method of the reliability analysis for a single device or a single bay has been studied extensivel y,the method for the entire substation automation system is still very limited so far.This paper analyzes the typical architecture of the digital substation,and shows the main methods to improve the reliability of the system.A method to calculate the reliability indices of the entire substation is then introduced.The method divides the digital substation system into communication systems,control systems,protection systems and station level system.Firs t,the availability block diagram is employed to calculate the reliability indices for each subsystem,and then the reliability indices of the entire substation are deduced.To demonstrate the metho d,the reliability indices of a typical digital substation are calculated and discussed.T he result shows that the reliability of the digital substation system can meet the requirements of IEC 61508 after adopting a reasonable device redundancy and network redundancy based on IEC 62439-PRP.
出处 《电力系统保护与控制》 EI CSCD 北大核心 2010年第14期34-38,共5页 Power System Protection and Control
基金 国家自然科学基金项目(50807037)~~
关键词 IEC61850 数字化变电站系统 可靠性 可用性框图 并行冗余协议 IEC 61850 digital substation system reliability availability block diagram parallel redundancy protocol
  • 相关文献

参考文献14

  • 1高翔,张沛超.数字化变电站的主要特征和关键技术[J].电网技术,2006,30(23):67-71. 被引量:430
  • 2Keiichi Kaneda,Setsuo Tamura,Nobuhisa Fujiyama,et al.IEC 61850 based substation automation system[C].// Power System Technology and IEEE Power India Conference.2008.
  • 3Singh C,Patton A D.Protection system reliability modeling:unreadiness probability and mean duration of undetected faults[J].IEEE Trans Rel,1980,29(4):339–340.
  • 4Anderson P M,Agarwal S K.An improved model for protective system reliability[J].IEEE Trans Rel,1992,41(3):422–426.
  • 5Kumm J J,Hou D,Schweitzer E O.Predicting the optimum routine test interval for protective relays[J].IEEE Trans on Power Delivery,1995:659–665.
  • 6王钢,丁茂生,李晓华,肖霖.数字继电保护装置可靠性研究[J].中国电机工程学报,2004,24(7):47-52. 被引量:144
  • 7IEC 61508 functional safety of programmable electronic safety related systems[S].
  • 8IEC 60870-4 telecontrol equipment and systems:part 4-performance requirements[S].
  • 9徐立子.变电站自动化系统的可靠性分析[J].电网技术,2002,26(8):68-72. 被引量:33
  • 10张沛超,高翔,顾黄晶,霍超.全数字化保护系统的主要问题及解决方案[J].电力自动化设备,2007,27(6):104-107. 被引量:38