期刊文献+

云广±800kV直流系统滤波器组投切控制策略优化 被引量:13

Optimization of Switching Control for AC Filter Groups in Yunnan-Guangdong ±800 kV DC System
下载PDF
导出
摘要 云广±800kV直流换流站内交流滤波器组容量大、投切频繁,其控制策略的优劣将直接影响到直流系统、甚至整个电网的稳定运行。分析了云广直流系统用于控制滤波器投切的无功控制、电压控制和谐波性能控制,并讨论了双套直流站控系统故障情况下滤波器由极控接口屏6MD66进行控制的参数设定原则及实现方法。针对云广直流工程试运行期间滤波器控制出现的问题,提出了相关的优化控制逻辑建议。 The AC filter groups at converter stations of Yunnan-Guangdong ±800 kV DC project are characterized with large capability and switching frequently,and the control strategy for them is meaningful to the stability of the DC system,even the whole grid.This paper analyzed the reactive power control,voltage control and harmonic performance control for the AC filter groups switching of the DC project,and discussed the principle of parameters setting and performance of the AC filter groups with 6MD66 in the pole control interface in the case where two station control systems failed.In order to solve the problems occurred during the trial operation of the DC project,certain suggestions to optimize the control logic of the AC filter groups are presented.
出处 《南方电网技术》 2010年第4期40-43,共4页 Southern Power System Technology
关键词 特高压直流系统 滤波器 投切控制 控制策略 试运行 UHVDC system AC filter switching control control strategy trial operation
  • 相关文献

参考文献2

二级参考文献3

  • 1陈亦平.直流系统无功控制对交流系统电压调整的影响分析.南方电网技术研究,2005,.
  • 2PTDH171/P-000088/ED1.020.AZ- a Study Reports Reactive Power Management[Z].
  • 3PTDH171/P-000088/ED4.321.AZ- 0 C / P Design Specifications DC Station Control[Z].

共引文献29

同被引文献146

引证文献13

二级引证文献92

相关作者