为研究气体绝缘全封闭式组合电器(gas insulated switchgear,GIS)设备中绝缘子表面固定金属颗粒沿面局部放电发展的现象及其特征,搭建了一套220 kV GIS设备沿面放电缺陷发展实验平台,采用逐步升压法对绝缘子表面固定金属颗粒的沿面局部放电进行长期试验,观察到了放电起始、发展直至沿面闪络的现象。利用测量到的局部放电随时间变化的趋势图、散点图、二维柱状图、灰度图,描述了沿面局部放电发展的现象并获得了相应的图谱特征。试验结果表明:GIS设备绝缘子表面固定金属颗粒沿面局部放电发展现象呈现出电晕放电、电晕放电和沿面流注放电共存、沿面流注放电3个主要阶段。
The surface partial discharge triggered by immobilized metal particles on gas insulated switchgear(GIS) insulators in terms of the discharge phenomena alongside its evaluation process was studied in this paper.With application of incremental voltages,long-term laboratory tests were conducted on a well-established 220 kV experimental platform to observe the entire evaluation process of surface partial discharge from its initiation,to gradual development and the eventual occurrence of surface flashover.Features of surface partial discharge phenomena at various evolutionary stages were recorded in the form of frequency curves,scatter diagrams,two-dimensional histograms,and grey-scale maps.It was shown by experiments that the phenomena of the surface partial discharge triggered by immobilized metal particles on GIS insulators indicates three developing stages from corona discharge domination,to coexistence of corona discharge and surface streamer discharge,and finally,surface streamer discharge domination.
出处
《中国电机工程学报》
EI
CSCD
北大核心
2011年第1期101-108,共8页
Proceedings of the CSEE
基金
国家重点基础研究发展计划项目(973项目)(2009CB-724508)~~
关键词
气体绝缘组合电器
局部放电
固定金属颗粒
绝缘子
沿面放电
gas insulated switchgear(GIS)
partial discharge
immobilized metal particles
insulator