摘要 雷电绕击是影响高压输电线路安全稳定运行的关键因素之一,减少地线保护角是降低绕击跳闸率的重要手段。为此,介绍了基于先导发展模型的超高压线路雷电绕击跳闸率分析方法,利用该方法对不同地形条件下各种塔型减小保护角对改善线路防雷性能的效果进行计算和对比,提出减小保护角的改造方案,对杆塔的力学性能进行校核,评估了减小保护角的经济费用,对比了减小保护角与其他防雷措施的技术经济性。研究表明,绕击跳闸率与塔型和地形关系密切,一般来说同一塔型保护角越小绕击跳闸率也越小,但不同塔型相同保护角跳闸率差异可能很大;减小保护角对改善线路防雷性能的效果受地形影响明显;对比不同防雷措施的效果和成本可见,将地线水平宽度增加对改善跳闸率的综合效果较好。 Lightning shielding failure is a key problem affecting operation safety of transmission lines,and reducing shielding angles is an important measure to restrain shielding failure rate.The shielding failure rate analyzing method for very high voltage transmission lines based on the leader progress model was introduced.By this method,effects of reducing shielding angles on different types of towers in various terrains were calculated and compared.An improved scheme of reducing shielding angles was proposed,and mechanical properties of the tower were analyzed.The cost of reducing shielding angle was evaluated,and its technical economy was compared to other lightning protection measures.Results show that shielding failure rate is closely related with tower types and terrains.In general,for the same tower,the shielding failure rate decreases with the decreasing of shielding angle,while for different towers,the shielding failure rates under the same shielding angle can be quite different.Effects of reducing shielding angle depend on the terrains.By comparing effects and costs of different lightning protection measures,it can be seen that increasing the distance of the ground lines is the optimal choice.
出处 《高电压技术》 EI CAS CSCD 北大核心 2011年第3期622-628,共7页 High Voltage Engineering
关键词 先导发展模型 输电线路 绕击 保护角 技术经济分析 雷电防护 leader progress model transmission line shielding failure shielding angle technical economy analysis lightning protection
  • 相关文献

参考文献24

  • 1维列夏金,吴维韩.俄罗斯超高压和特高压输电线路防雷运行经验分析[J].高电压技术,1998,24(2):76-79. 被引量:188
  • 2WANG Zhi-yong, WANG Shao an, YU Zhan qing, et al. Ana lysing on characteristics of lightning shielding failure of UHVAC double circuit transmission line based on leader progression method [C]// Proceedings of Asia-Pacific International Symposium on Electromagnetic Compatibility, Beijing, China: Tsing- hua University, 2010: 1582-1585.
  • 3LI Zhi zhao, WANG Zhi-yong, ZENG Rong, et al. Research on characteristics of conductor surface electric field considering downward lightning leader[C]// Proceedings of Asia Pacific International Symposium on Electromagnetic Compatibility, Beijing, China: Tsinghua University, 2010: 1325-1328.
  • 4谷山强,陈家宏,陈维江,李晓岚,童雪芳,张瑞.输电线路防雷性能时空差异化评估方法[J].高电压技术,2009,35(2):294-298. 被引量:88
  • 5谭进,张焕青,刘玉君,梁舰,唐程,刘刚.±500kV三沪Ⅱ回同塔双回直流输电线路防雷分析[J].高电压技术,2010,36(9):2173-2179. 被引量:29
  • 6CHEN S M, Du Y, Fan L M dong lightning location system et al. Evaluation of the Guangwith transmission line fault data [J]. IEE Proceedings of Science, Measurement and Technolo gy, 2002, 149(1): 9-16.
  • 7Udo T. Switching surge and impulse sparkover characteristic of large gap spacing and long insulator strings[J]. IEEE Transaction on Power Apparatus and Systems, 1965, 84(4): 304-309.
  • 8Udo T. Sparkover characteristics of large gap spaces and long insulation springs[J]. IEEE Transaction on Power Apparatus and Systems, 1964, 83(5): 471-482.
  • 9Pigini A. Performance of large air gaps under lightning overoltages: experimental study and analysis of accuracy of predetermi- nation methods [J]. IEEE Transaction on Power Delivery, 1989, 4(2): 1379-1392.
  • 10YU Zhan qing, HOU Mu-wu, ZENG Rong, et al. Numerical analysis models of lightning transient for transmission lines considering lightning induced voltage[C]// Proceedings of 12th Asian Conference on Electrical Discharge. Shenzhen, China: Tsinghua University, 2004: 625-628.