期刊文献+

寒区调峰型地表水源热泵系统的供热性能研究 被引量:2

Study on heating performance of peak-shaving surface water heat pump system in cold area
下载PDF
导出
摘要 地表水源热泵具有重要节能环保与经济意义,但寒区冬季水温过低导致常需采用调峰型地表水源热泵系统.在介绍前置式系统和后置式系统两种形式的基础上,对调峰运行阶段的系统供热运行性能作了数学建模,并结合算例作了比较分析.结果表明后置式系统的运行性能与经济性均较好,每个供暖期可节省运行费6.65元/m2,这为系统方案的设计提供了有益的指导. The surface water source heat pump plays a significant role on the energy conservation and environmental protection as well as the economy.But in the cold area it is excessive to add peak-shaving heat source for water temperature is often low in winter.This paper introduced two operating modes of the peak-shaving surface water heat pump system,and deduced their operating cost models in heating period.With a calculation example,illuminated that the post-located system was superior and preferential on economy than fore-located one with 6.65 Yuan /m2 saving in the operating cost,which provided a beneficial instruction for the design.
出处 《哈尔滨商业大学学报(自然科学版)》 CAS 2011年第1期112-116,共5页 Journal of Harbin University of Commerce:Natural Sciences Edition
基金 黑龙江省教育厅科学技术研究项目(11551114)
关键词 地表水源热泵 调峰型 供热 运行性能 surface water source heat pump peak-shaving heating operating performance