摘要 提出了一种新的输电线路故障定位算法,该算法利用故障时正、负序网络中各自电压、电流间的关系,导出了故障定位方程。无需线路参数,只需借助GPS实现同步采集线路两端的电压、电流数据,并作相关处理,即可实现故障定位。与传统方法相比,该算法不受线路参数变化、故障发生地点环境以及故障过度电阻等的干扰,实现简单、灵活,实用性更强。同时利用Matlab软件对算法做了大量仿真测试,测试结果证明了该算法的正确性。 A new fault location algorithm for transmission lines is introduced,the fault location equation is derived from the relationship between the voltages and currents of positive sequence and negative sequence networks when fault happened.This method does not require line parameters,only by means of the GPS synchronization to acquire the voltages and currents data at both ends of the transmission line,and does some related processing about these data,then the location equation can be realized easily.Compared with traditional methods,this algorithm is not only uninfluenced by the disturbances of the changes of transition lines,the fault location and its environment and the fault resistances,but also simple,are flexible and more useful.The simulation results show the correctness of the algorithm.
作者 徐俊明
出处 《电气传动自动化》 2011年第2期27-30,共4页 Electric Drive Automation
关键词 输电线路 故障定位 GPS 同步 transmission line fault location GPS synchronization