期刊文献+

220kV架空线路故障断线原因试验检测分析 被引量:10

Causation Analysis by Test and Detection on Break Fault of 220kV Overhead Transmission Line
下载PDF
导出
摘要 介绍了220kV线路断线故障经过和临时处理措施,通过对断线样品进行拉力、通流、电镜和能谱分析等机械、电气性能对比试验和检测,分析导线断线原因。指出故障前断口处导线已存在显著的通流缺陷,同时由于线路运行年限较长机械强度下降,因局部发热恶性循环发展和强度逐步丧失最终导致小负荷电流下导线断线。强调要控制线路负荷和加强红外测温,及时消除线路安全隐患,并尽快实施故障线路技改工程。 The paper introduces line break failure and temporary treatment measures of 220 kV overhead transmission line, then gives the reasons for disconnection of wires through performance mechanical and electrical comparison tests of the broken samples such as pull test, current carrier and temperature rising test, electron microscopy test and energy spectrum analysis. Points out that as a long line running years, the wire had existed significant defects of machinery and electricity before the fracture, and then led to wire break under a small load current due to vicious cycle of local heat development and gradual loss of strength. At the end this paper, stresses the need to control load current and infrared temperature measurement to remove security risks of line, and suggests taking out technical transformation project of fault line as soon as possible.
作者 彭向阳
出处 《高压电器》 CAS CSCD 北大核心 2011年第6期48-52,57,共6页 High Voltage Apparatus
关键词 输电线路 断线故障 试验检测 原因分析 overhead transmission line wire breaking fault test and detection causation analysis
  • 相关文献

参考文献14

二级参考文献74

共引文献213

同被引文献136

引证文献10

二级引证文献46

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部