变电站设备外绝缘状态在线评估系统研发 被引量:5

Development on the Online Evaluation System of Equipment’s External Insulation Status in Substations
下载PDF
导出
摘要 为了有效预防变电站设备闪络事故的发生,根据最大泄漏电流和污闪电压关系建立了变电站设备外绝缘状态评估模型。该模型以一段时间内测得的绝缘子泄漏电流最大值为基础,综合地考虑了绝缘子形状系数、爬电总距离和现场相对湿度的影响。利用这个评估模型研发了变电站设备外绝缘状态在线评估系统。该系统在人工试验和现场运行中显示,能实时、正确地评估设备的污秽状态。 In order to effectively prevent the flashover accidents of equipments in substations,an evaluation model for the equipment’s external insulation status is built up according to the relationship of flashover voltage and maximum leakage current.The model is based on the maximun leakage current of insulators measured during a period of time,and takes the integrated effects of the shape factors,total cleepage distance and relative humidity level into account.An online evaluation system of equipment’s external insulaton status in substations is developed with the proposed model.Artificial experiments and operation practices show that the online evaluation system is able to correctly make a real-time evaluation to the insulation status of the equipments.
出处 《南方电网技术》 2011年第3期78-82,共5页 Southern Power System Technology
基金 国家重点基础研究发展计划项目(973项目)资助(2009CB724503)~~
关键词 变电站 外绝缘状态 在线评估系统 绝缘子 泄漏电流 闪络 substation external insulation status online evaluation system insulator leakage current flashover
  • 相关文献

参考文献5

二级参考文献39

  • 1关志成,张仁豫,薛家麒,马霜,李楠.自然污秽可溶盐构成及其对污闪电压值的影响[J].电瓷避雷器,1989(6):13-18. 被引量:44
  • 2张建兴,律方成,刘云鹏,谭磊,赵亚平.高压绝缘子泄漏电流与温、湿度的灰关联分析[J].高电压技术,2006,32(1):40-41. 被引量:31
  • 3清华大学 西安交通大学.高电压绝缘[M].北京:水利电力出版社,1986..
  • 4徐通训 徐喜佑.电力设备防污闪技术[M].能源部电力司,1995..
  • 5宿志一 刘思湄.大气环境对输变电设备抗污闪能力的影响:电科院技术报告G9534[R].,1995..
  • 6华北污闪事故调查组.一九九零年华北大面积污闪事故调查报告[R].,1990..
  • 7.国家电力公司发输电部二00一年初辽宁、华北和河南电网大面积污闪事故调查报告[R].,2001..
  • 8Kumosa L, Armentrout D, Benedikt B, et al. An investigation of moisture and leakage currents in GRP composite hollow cylinders[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2005, 12(5): 1043-1059.
  • 9Karady G. The effect of fog parameters on the testing of artificially contaminated insulators in a fog chamber [J].IEEE Transactions on Power Apparatus and Systems, 1975, 94(2) 378-387.
  • 10Kumagai S. Influence of algal fouling on hydrophobicity and leakage current on silicone rubber[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2007, 14(5): 1201-1206.

共引文献303

同被引文献41

  • 1孙强,黄宗君,韩绍周,朱岸明,马江泓,李云阁,李海波.一起800kV高压套管绝缘故障的原因分析[J].电网与清洁能源,2010,26(3):12-15. 被引量:21
  • 2焦尚彬,刘丁,郑岗,李琦.基于遥测技术的输电线路绝缘子污秽在线监测系统[J].电力系统自动化,2004,28(15):71-75. 被引量:26
  • 3牛保红,阳少军.天生桥二级水电厂~#2变压器事故原因分析[J].高电压技术,2007,33(1):143-147. 被引量:10
  • 4周利军,汤浩,吴广宁,王云飞.油纸绝缘微水扩散的稳态分布[J].高电压技术,2007,33(8):27-30. 被引量:35
  • 5FERNANDO M A R M, GUBANSKI S M. Leakage current patterns on contaminated polymeric surfaces E J]. IEEE Transac- tion on Dielectrics and Electrical Insulation, 1999, 6(6) : 689 - 694.
  • 6ALMAD A S, GHOSH P S, AHMAD H, et al. Assessment of ESDD on high-voltage insulators using artificial neural network EJ~. Electric Power Systems Research, 2004, 72(2): 131 136.
  • 7ALMAD A S, AHMAD H, SALAM M A, et al. Prediction of salt contamination on high voltage insulators in rainy season u- sing regression technique [ C ]// Proceedings of TENCON, 24 Sep 2000-27 Sep 2000, Kuala Lumpur, Malaysia: 2000, 3: 184 189.
  • 8IEC 60507-1991, Artifical pollution tests on high-voltage insu- lators to be used on AC systems[ S ].
  • 9GB/T45852-2004,交流系统用高压绝缘子德人工污秽实验[S].北京:中国标准出版社,2004.
  • 10剂其昶.电气绝缘结构设计原理[M].北京:机械工业出版社,1988.