国外对特高压输电线路雷击跳闸原因的一个新观点 被引量:65

A NEW VIEWPOINT ABOUT LIGHTNING TRIP-OUT OF UHV TRANSMISSION LINES
下载PDF
导出
摘要 介绍了国外在分析特高压输电线路雷击跳闸原因时提出的一个新观点 ,即雷电击中档距中间部位的避雷线会引起避雷线—相导线间隙击穿放电 ,进而引起线路跳闸。采用避雷线负保护角并不能避免这种放电发生。提高避雷线保护的有效性可以通过减小避雷线—相导线间隙击穿概率来达到。 A new viewpoint put forward by foreign researchers about lightning trip out of UHV transmission lines is presented in this paper. The lightning trip out of UHV transmission lines is considered to be caused mainly by discharge of the gap between shielding wire and phase conductor while lightning strikes onto the shielding wire at mid span, and this kind of discharge cannot be avoided under negative shielding angles. Effective shielding can be achieved by reducing the breakdown probability of the gap between shielding wire and phase conductor.
作者 李培国
出处 《电网技术》 EI CSCD 北大核心 2000年第7期63-65,共3页 Power System Technology
关键词 特高压输电线路 雷击跳闸 避雷线 绝缘子 lightning trip out lightning performance UHV transmission line
  • 相关文献

参考文献2

  • 1[3]Dyakov A F,Nikitin O A,Maximov B K,et al.Analysis of lightning protection of 500~1150kV power transmission lines.10th ISH, Montreal, 1997
  • 2[4]Anderson R S,Eriksson A J.Lightning parameters for engineering application.Electra, 1980, 69.