期刊文献+

基于GIS制造特征的电磁波仿真模型简化的研究 被引量:1

The Research of Gas Insulated Switchgear Model Simplification and Its Influence on Simulation Result Based on Manufacturing Feature
下载PDF
导出
摘要 以CAD特征建模方法为基础,建立了GIS电磁波传播仿真研究的逆向建模方法。应用三维电磁场数值计算有限元方法,在准确考虑GIS内部绝缘子和内导体制造特征的前提下,分析了一实际GIS内电磁波传播规律,获得了电磁波的泄漏参数的频率特性。研究了GIS内部绝缘子和内导体制造特征不同简化模型中泄漏参数的频率特性。将不同简化模型分析结果与精确模型的分析结果进行对比,分析了GIS制造特征的不同程度的简化对电磁波泄漏参数的频率特性、数值仿真计算时间和占用内存的影响。基于上述讨论,通过系统的比较,确定最优简化模型。由于特征建模和电磁分析模型简化中所遵循的几何构建过程是相似的,所以该简化思路在一定范围内具有通用性。 CAD manufacturing features based modeling method is used in studying propagation of EM-field in gas insulated switchgear(GIS).We take inverting mode to simplify the model of GIS step by step.A precision analysis model was established based on a practical 252kV GIS blueprint,and the frequency characteristic of EM leakage has been simulated using the finite element method.Different levels of simplification based on manufacturing features were carried out on this practical GIS.After systematic comparison,the influence of manufacturing feature simplification on computation of leakage of EM-wave was studied.The balance between the calculation accuracy and computing speed is considered.The results offer a scientific and systematic simplification method for calculating EM leakage of the GIS for further GIS design or simulation.Because the construction processes of feature modeling and EM model are the same,the presented method for modeling GIS has general purpose.
作者 卢斌先 孟准
出处 《电工技术学报》 EI CSCD 北大核心 2013年第1期119-125,共7页 Transactions of China Electrotechnical Society
基金 国家高技术研究发展计划(863计划)(2011AA05A12)资助项目
关键词 气体绝缘变电站(GIS) 电磁波传播规律 电磁波泄漏 模型简化 有限元计算 Gas insulated switchgear(GIS),leakage of EM-wave,propagation characteristics of EM,model simplification,finite element method(FEM)
  • 相关文献

参考文献14

  • 1Shuhei Kaneko,Shigemitsu Okabe. Electromagnetic wave radiated from an insulating spacer in gas insulated switchgear with partial discharge detection[J].IEEE Transactions on Dielectrics and Electrical Insulation,2009,(01):60-68.
  • 2Manabu Yoshimura,Hirotaka Muto,Chieko Nishida. Propagation properties of electromagnetic wave through T-branch in GIS[J].IEEE Transactions on Dielectrics and Electrical Insulation,2007,(02):328-333.doi:10.1109/TDEI.2007.344610.
  • 3Shigemitsu Okabe,Shuhei Kaneko. Partial discharge diagnosis method using electromagnetic wave mode transformation in gas insulated switchgear[J].IEEE Transactions on Dielectrics and Electrical Insulation,2007,(03):702-709.doi:10.1109/TDEI.2007.369534.
  • 4Shigemitsu Okabe,Shuhei Kaneko,Manabu Yoshimura. Propagation characteristics of electromagnetic waves in three-phase-type tank from viewpoint of partial discharge diagnosis on gas insulated switchgear[J].IEEE Transactions on Dielectrics and Electrical Insulation,2009,(01):199-205.
  • 5Masayuki Hikita,Shinya Ohtsuka,Takeshi Teshima. Electromagnetic(EM)wave characteristics in GIS and measuring the EM wave leakage at the spacer aperture for partial discharge diagnosis[J].IEEE Transactions on Dielectrics and Electrical Insulation,2007,(02):453-460.doi:10.1109/TDEI.2007.344624.
  • 6Shuhei Kaneko,Shigemitsu Okabe,Manabu Yoshimura. Partial discharge diagnosis method using electromagnetic wave mode transformation in actual GIS structure[J].IEEE Transactions on Dielectrics and Electrical Insulation,2008,(05):1329-1339.
  • 7Shigemitsu Okabe,Shuhei Kaneko. Electromagnetic wave propagation in a coaxial pipe GIS model[J].IEEE Transactions on Dielectrics and Electrical Insulation,2007,(05):1161-1169.doi:10.1109/TDEI.2007.4339476.
  • 8Toshihiro Hoshino,Katsumi Kato,Naoki Hayakawa. Frequency characteristics of electromagnetic wave radiated from GIS apertures[J].IEEE Transactions on Power Delivery,2001,(04):552-557.doi:10.1109/61.956736.
  • 9M Sawada;K Omori;S Isejimal.Influence of metal flange cover of insulation spacers on propagation properties of PD-induced electromagnetic wave in GIS[A]北京,2008437-442.
  • 10Shinya Ohtsuka,Takashi Teshima,Satoshi Matsumoto. Relationship between PD induced electromagnetic wave measured with UHF method and charge quantity obtained by PD current waveform in model GIS[A].2006.615-618.

二级参考文献31

  • 1钱勇,黄成军,江秀臣,肖燕.基于超高频法的GIS局部放电在线监测研究现状及展望[J].电网技术,2005,29(1):40-43. 被引量:166
  • 2李信,李成榕,李亚莎,王伟,李海亮.有限时域差分法对GIS局部放电传播的分析[J].中国电机工程学报,2005,25(17):150-155. 被引量:49
  • 3黄兴泉,康书英,李泓志,张欲晓.GIS局部放电超高频电磁波的传播特性研究[J].高电压技术,2006,32(10):32-35. 被引量:37
  • 4Sakakibara T, Murase H, Haginomori E, et al. Study of propagation phenomena of partial discharge pulses in gas insulated substation[J]. IEEE Transactions on Power Delivery, 1998, 13 (3) : 768-776.
  • 5Judd M D, Farish O, Hampton B F. The excitation of UHF signals by partial discharges in GIS[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 1996, 3(2):213-228.
  • 6Hoshino T, Kato K, Hayakawa N, et al. A novel technique for detecting electromagnetic wave caused by partial discharge in GIS[J]. IEEE Transactions on Power Delivery, 2001, 16(4) :544-551.
  • 7Anon. Partial discharge testing of gas insulated substations[J]. IEEE Transactions on Power Delivery, 1992, 7(2):499-506.
  • 8Huecker T, Gorablenkov J. UHF partial discharge monitoring and expert system diagnosis[J]. IEEE Transactions on Power Delivery, 1998, 13(4):1162-1167.
  • 9Pryor B M. Review of partial discharge monitoring in gas insula ted substations[C]// Science, Education and Technology Division Colloquium on Partial Discharges in Gas Insulated Substations. London, UK: [s. n. ], 1994:1-2.
  • 10Hoshino T, Koyama H, Maruyama S, et al. Comparison of sensitivity between UHF method and IEC 60270 for onsite calibration in various GIS[J]. IEEE Transactions on Power Delivery, Z006, 21(4): 1948-1953.

共引文献70

同被引文献9

引证文献1

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...