摘要
根据无填料喷雾冷却塔的散热理论,建立了无填料喷雾冷却塔的热力模型,并通过多组试验数据验证了热力模型的准确性,结果表明:出塔冷却水温度的理论计算值与试验测试结果的相对误差在2.0%之内,理论计算结果与试验结果吻合。
According to the principle of heat-dissipation, the thermal model of the no-padding and spraying cooling tower was established. And through several experimental datas the accuracy of thermal model was verified. The results showed: The theoretical valve of the outlet cooling water temperature in the no-padding and spraying cooling tower was agree with the experimental results, and the absolute relative errors were within 2.0% between the two.
出处
《洁净与空调技术》
2013年第2期25-27,共3页
Contamination Control & Air-Conditioning Technology
关键词
无填料喷雾冷却塔
水滴
热力模型
试验验证
No-padding and spraying cooling tower
Water droplet
thermal model
Test verification