利用故障分量瞬时值的电流纵差保护新判据 被引量:15

A NEW CRITERION FOR LINE CURRENT DIFFERENTIAL PROTECTION BY USING INSTANTANEOUSVALUE OF FAULT COMPONENT
下载PDF
导出
摘要 GPS时钟同步技术在电流纵差保护中的成功应用 ,为利用瞬时值进行动作判定提供了条件。针对工频相量差动判据存在的问题 ,提出一种基于故障分量瞬时值的电流纵差保护新判据。该判据在保证区外故障稳定性的基础上 ,对区内故障特别是高阻故障具有很强的反应能力和较快的动作速度。基于 EMTP的数字仿真结果和动模试验均验证了该判据的正确性。 Since the GPS based clock synchronization technique has been successfully applied in line current differential protection,it's possible to make tripping decision by using instantaneous value of fault component.To solve the problems existing in conventional phasor differential criterion,this paper proposes a new criterion based on the instantaneous value of fault com ponent. On the basis of keeping stable against external faults,this criterion has the features of strong ability to response to internal faults,especially to the high resistance faults.Both the EMTP sim ulation and dynam ic simulation test have shown its correctness. This is the project of State Key Technology Development Program No.96 BK- 10 6 - 4- 1 .
作者 高厚磊
出处 《电力系统自动化》 EI CSCD 北大核心 2000年第16期21-24,54,共5页 Automation of Electric Power Systems
基金 国家重点技术发展项目专项课题!(96 BK- 10 6 - 4- 1)
关键词 电流差动保护 故障分量瞬时值 电力系统 current differential protection operating criterion fault component instantaneous value
  • 相关文献

参考文献2

二级参考文献9

  • 1田晓玫,马天皓,陈德树,张乾亨.数字式光纤纵差保护的研究[J].光通信研究,1993(1):55-58. 被引量:1
  • 2许继电器股份有限公司.-[J].WXH-35型微机短线路保护装置,1995,.
  • 3山东工业大学.ABB公司REL561型分相电流差动保护装置介绍及动模试验报告[M].,1995..
  • 4山东工业大学,ABB公司REL561型分相电流差动保护装置介绍及动模试验报告,1995年
  • 5许继电器股份有限公司,WXH-35型微机短线路保护装置,1995年
  • 6田晓玫,光通信研究,1993年,1
  • 7王旭昭,继电器,1991年,4期
  • 8南京自动化研究所(译),LFCB102型数字电流差动保护使用说明书,1989年
  • 9王绪昭,伍叶凯,杨奇逊.一种适用于双端系统微机微波电流差动保护的跳闸判据[J].继电器,1991,19(4):2-8. 被引量:11