500kV变电站主变套管油色谱异常分析及处理 被引量:2

Analysis and Treatment of Abnormal Oil Chromatogram of Main Transformer Bushing in 500 kV Substation
下载PDF
导出
摘要 500 kV平果变电站P2B号主变压器的油色谱试验结果显示,中压侧B相套管的乙烷含量超标。通过分析该套管历年的试验数据及红外巡检情况,根据相关国标及行标判断该套管存在中温过热现象,建议立即更换。 Test results of oil chromatogram of No.2 PB transformer in 500kV Pingguo substation show that the content of ethane of phase B bushing on the medium voltage side is over limit. According to the analysis of test data of the bushing and infrared detection result, and based on national and industry standard, it is judged that the bushing has overheat phenomenon at medium temperature. It is suggested that the bushing be replaced.
作者 杨捷 黎大健
出处 《广西电力》 2013年第3期34-35,共2页 Guangxi Electric Power
关键词 主变压器套管 油色谱 红外检测 main transformer bushing oil chromatogram infrared detection
  • 相关文献

参考文献3

  • 1Q/CSG114002-2011,电力设备预防性试验规程[S].
  • 2GB/T725-2001.变压器油中溶解气体分析和判断导则[S].
  • 3GB/T24624-2009.绝缘套管油为主绝缘(通常为纸)浸渍介质套管中溶解气体分析(DGA)的判断导则[S].