期刊文献+

GIS局部放电与等效脉冲注入过程中特高频信号一致性研究 被引量:5

Study on the Consistency of Ultra-high Frequency Signals Produced by GIS Partial Discharge and the Process of Equivalent Pulse Injection
下载PDF
导出
摘要 笔者对GIS局部放电与等效脉冲注入过程中的特高频信号一致性进行了试验研究。通过测量等效脉冲注入和局部放电信号的电磁波波形,发现传感器耦合到的特高频信号波形相似;在相同试验条件下,局部放电信号与等效脉冲注入产生的特高频信号衰减规律和传播范围相同。试验结果表明,局部放电与等效脉冲注入过程中产生的特高频信号一致性很好。在此基础上,通过建立等效脉冲幅值与局部放电量之间的对应关系,可用于GIS局部放电特高频在线监测装置现场校验。 This paper proposed to adopt a method called Equivalent Pulse Injection (EPI)to fix the criterion and conducted an investigation into the consistency of UHF signals produced by the GIS PD and the process of EPI. By measuring the waveforms of electromagnetic waves of EPI and real GIS PD,it is found that the pulse signals waveforms coupled by the UHF sensor are accordant. Under the same research conditions, the signal attenuation characteristic of real PD and the EPI injection show high consistency and they have a same available measure range. The research results show that EPI method and real PD signal measure are very consistent,so the EPI can be adopted to fix the criterion of UHF signal on-line monitoring of GIS PD on the spot.
出处 《高压电器》 CAS CSCD 北大核心 2013年第11期99-103,共5页 High Voltage Apparatus
关键词 GIS 局部放电 特高频检测 等效脉冲注入法 GIS partial discharge ultra-high frequency (UHF) monitoring equivalent pulse injection
  • 相关文献

参考文献18

  • 1DL/T617-2010.气体绝缘金属封闭开关设备技术条件[S].
  • 2卢启付,李兴旺,徐晓刚,吕鸿,王宇,程养春.基于ANSYS的GIS隔离开关短路事故分析[J].高压电器,2012,48(8):76-79. 被引量:16
  • 3卢启付,李兴旺,程养春,谢志扬,金向朝.气体绝缘金属封闭开关设备接地开关短路事故分析[J].广东电力,2011,24(11):106-108. 被引量:9
  • 4李兴旺,卢启付,梁如清GIS局部放电检测技术及应用[C]∥中国电机工程学会高电压专业委员会2011学术会议.山东:[出版地不详],2011.
  • 5李兴旺,卢启付,吕鸿,王宇,王流火.气体绝缘开关设备局部放电特高频在线监测技术及应用[J].广东电力,2012,25(6):91-95. 被引量:15
  • 6夏建中,李洪臣.对电力电容器局部放电的理解与对策[J].电力电容器与无功补偿,2009,30(2):7-9. 被引量:36
  • 7HAMPTON B F, MEATS R J. Diagnostic measurenment at UHF in gas insulated substations[J]. IEE Proceedings, 1988, 135(2): 137-145.
  • 8MARTIN D J, FARISH O, HAMPTON B F. Broadband couplers for UHF detection of partial discharge in gas- insulated substation[J]. IEEE Proc-sci. Meas. Technology, 1995,142(3):237-243.
  • 9JUDD M D, FARISH O, HAMPTON B F. The excitation of UHF signals by partial discharges in GIS[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 1996,3(2) :213-228.
  • 10KURRER R, FESER K. The application of ultra-high- frequency partial discharge measurements to gas-insulated substations[J]. IEEE Transactions on Power Delivery, 1998, 3(12) : 777-782.