混凝土辐射供冷RC简化传热模型的改进及实验验证 被引量:4

Improvement and Experimental Validation of Modified RC-Network Model for Concrete Core Cooling Slab
下载PDF
导出
摘要 混凝土辐射供冷非稳态传热过程的研究,对系统的运行和控制具有重要意义.本文对以系统几何及热工参数来确定核心温度层热容热阻的RC简化模型进行研究,加入沿管道供水换热过程的模型,实现供水温度和流量联合变化工况下楼板动态热响应的模拟分析.搭建混凝土辐射供冷系统全尺寸标准测试舱,验证上述模型的准确性和适用性.结果表明,在供水温度和流量非连续变化的非稳态工况下,模型计算值与实测值变化趋势基本一致,热流密度模拟值与实测值偏差约为5,W/m2,内部温度模拟值与实测值偏差小于等于0.5,℃,模拟误差小,适用性较高. The unsteady heat transfer of concrete core cooling is of great significance in the operation and control of the system. In this paper, RC-network method is adopted to realize the optimization research, in which thermal ca- pacity and resistance of core temperature layer are determined with geometric and thermal parameters, the model of heat transfer process is added along the water supply pipe, and the simulation analysis is made of the dynamic ther- mal response of the floor under the combined change of water temperature and flow. In order to validate the model above, a full size standard test chamber of the concrete radiant cooling system is constructed. The result indicates that the simulation has good coincidence with the measurement in tendency under the unsteady condition of non-sequence change of supply water temperature and flow rate. The deviation of heat-flow density between simulation and meas- urement is about 5 W/m^2, and the deviation of inside temperature is no more than 0.5 ℃. The simulation error is small and applicability is high.
出处 《天津大学学报(自然科学与工程技术版)》 EI CAS CSCD 北大核心 2013年第12期1095-1100,共6页 Journal of Tianjin University:Science and Technology
基金 国家自然科学基金资助项目(51178298)
关键词 混凝土辐射供冷 非稳态传热 RC简化模型 实验验证 concrete core cooling unsteady heat transfer RC simplified model experimental validation
  • 相关文献

参考文献1

二级参考文献2

共引文献7

同被引文献29

  • 1马玉奇,刘学来,李永安,薛红香,张红瑞.冷却顶板空调系统热工参数分析[J].山东建筑大学学报,2007,22(5):425-429. 被引量:14
  • 2Sattari S,Farhanieh B. A parametric study on radiantfloor heating system performance[J]. RenewableEnergy,2006,1(10):1617-1626.
  • 3Olesen B W. Radiant floor cooling systems[J]. ASHRAEJournal,2008,50(9):16-20.
  • 4Fort K. Floor Heating and Hypocaust Stuttgart[M].Germany:Transsolar Nergietechnik GmbH,1999.
  • 5Jin X,Zhang X,Luo Y,et al. Numerical simulation ofradiant floor cooling system:The effects of thermal resistanceof pipe and water velocity on the performance[J]. Building and Environment,2010,45(11):2545-2552.
  • 6Weber T,Jóhannesson G. An optimized RC-network forthermally activated building components[J]. Buildingand Environment,2005,40(1):1-14.
  • 7Liu K X,Tian Z,Zhang C,et al. Establishment andvalidation of modified star-type RC model for concretecore cooling slab[J]. Energy and Buildings,2011,43(9):2378-2384.
  • 8Strand R,Pederson C. Modeling radiant systems in anintegrated heat balance based energy simulation program[J]. ASHRAE Transactions,2002,108(2):1-9.
  • 9Tian Z,Duan B D,Niu X L,et al. Establishment andexperimental validation of a dynamic heat transfer modelfor concrete radiant cooling slab based on reaction coefficientmethod[J]. Energy and Buildings,2014,82:330-340.
  • 10Wang S W,Chen Y M. Transient heat flow calculationfor multilayer constructions using a frequency-domainregression method[J]. Building and Environment ,2003,38(1):45-61.

引证文献4

二级引证文献8

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部