摘要
在不同的入口条件下,对金属铝箔填料在淋水密度为3600-6155kg/(m^2·h),迎面风速为2m/s情况下的耗水量及可间歇性供水时间进行了测试。通过测试分析得出在实验情况下,填料的耗水量为19-33L/h;可间歇性供水时间为5-10min。
Under the condition of different entry, aluminum foil packing at water spray density of 3600-6155kg/ ( m2· h), right against the face wind speed of 2 m/s, tested the water consumption and intermittent water supply time. Through test analysis under the condition of experiment, concluded that the water consumption is about 19-33L/h and the intermittent water supply time is about 5-10 minutes.
关键词
直接蒸发冷却
铝箔填料
耗水量
可间歇性供水时间
direct evaporative cooling
the aluminum foil packing
water consumption
intermittent water supply time