基于VSC-HVDC的风力发电系统低电压穿越协调控制 被引量:19

Coordinated LVRT control of wind power generation system based on VSC-HVDC
下载PDF
导出
摘要 提出一种适用于通过VSC-HVDC系统并网风电场的低电压穿越协调控制策略。建立高压直流输电线路和风电场的模型,分析电网故障期间系统的工作原理。低电压穿越期间,通过HVDC两端变流站提供无功支持,并采用基于电压控制的快速功率降低算法控制风电场馈入功率,维持直流系统功率平衡;对风电机组功率控制进行改进,提出分层控制与HVDC控制相协调,保持风电机组的电压稳定。算例仿真结果验证了该控制策略的快速性和有效性。 A coordinated control strategy is proposed for the LVRT(Low Voltage Ride Through)of wind farm with grid-connecting VSC-HVDC.The models for HVDC line and wind farm are built and the working principle of system during grid fault is analyzed.The converters at both sides of HVDC provide reactive power during LVRT and the fast power reduction based on voltage control is adopted to control the in-feed power of wind farm for the power balance of DC system.The hierarchical control is coordinated with the HVDC control to improve the power control of wind turbine for its voltage stability.The simulative results of case study verify the quickness and effectiveness of the proposed control strategy.
出处 《电力自动化设备》 EI CSCD 北大核心 2014年第3期138-143,共6页 Electric Power Automation Equipment
基金 国家高技术研究发展计划(863计划)项目(2011AA-05A107) 国家自然科学基金资助项目(51177015 51077068) 江苏省产学研前瞻性联合研究项目(BY2010142) 江苏教育厅自然科学基金资助项目(12KJB470006)~~
关键词 风电场 VSC-HVDC 低电压穿越 协调控制 分层控制 电压控制 高压直流输电 wind farms VSC-HVDC LVRT coordinated control hierarchical control voltage control HVDC power transmission
  • 相关文献

参考文献15

  • 1FELTES C,WREDE H,KOCH F,et al. Enhanced fault ride- through method for wind farms connected to the grid through VSC-based HVDC transmission[J]. IEEE Transactions on Power Systems, 2009,24 ( 3 ) : 1537-1546.
  • 2马文龙.Crowbar保护在双馈异步风力发电系统电网故障穿越中的应用[J].电力自动化设备,2011,31(7):127-130. 被引量:53
  • 3XU L,YAO L,SASSE C. Grid integration of large DFIG-based wind farms using VSC transmission[J]. IEEE Transactions on Power Systems, 2007,22 ( 3 ) : 976-984.
  • 4贺益康,周鹏.变速恒频双馈异步风力发电系统低电压穿越技术综述[J].电工技术学报,2009,24(9):140-146. 被引量:203
  • 5LI Jun,LI Dujiang,HONG Lei,et al. A novel power-flow balance LVRT control strategy for low-speed direct-drive PMSG wind generation system[C] //IECON 2010-36th Annual Conference on IEEE Industrial Electronics Society. Glendale,AZ,USA:[s.n.], 2010:748-753.
  • 6FELTES C,WREDE H,KOCH F,et al. Fault ride-through of DFIG-based wind farms connected to the grid through VSC-based HVDC link[C] //Proceedings of the 16th Power Systems Com- putation Conference. Glasgow,UK: PSCC,2008 : 1-7.
  • 7XIANG Daiwei,RAN Li,TAVNER P J,et al. Control of a doubly fed induction generator in a wind turbine during grid fault ride- through [J]. IEEE Transations on Energy Conversion,2006,21 (3) :652-662.
  • 8徐政,陈海荣.电压源换流器型直流输电技术综述[J].高电压技术,2007,33(1):1-10. 被引量:370
  • 9张永斌,袁海文.双馈风电机组低电压穿越主控系统控制策略[J].电力自动化设备,2012,32(8):106-112. 被引量:16
  • 10VRIONIS T D,KOUTIVA X I,VOVOS N A,et al. Control of an HVDC link connecting a wind farm to the grid for fault ride- through enhancement[J]. IEEE Transactions on Power Systems, 2007,22 (4) : 2039-2047.

二级参考文献141

共引文献740

同被引文献337

引证文献19

二级引证文献303

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部