变频压缩机频率与热泵空调各参数关联的研究 被引量:5

The Associated Research of Inverter Compressor Frequency and Heat Pump Air Condition Parameters
下载PDF
导出
摘要 本文使用DA108M1C-81FZ8压缩机在高频和低频运转范围内测试并分析其与输入功率、排气压力、吸气压力等的关联,并对不同频率下系统制热量、COP等进行测试分析。研究表明:在保持同一测试工况下,低频范围内25Hz作为一个低频节能峰值点,而在高频范围内85Hz作为一个高效运行峰值点;压缩机不同频率对于制热量的大小影响较大,随着频率的增加制热量随之增加;对COP的影响有两个抛物峰值,分别在低频和高频范围出现,即系统部分负荷的COP在一定的频率范围可以达到最大值,运转频率增大到一定程度后会系统性能降低。 This paper uses DA108M1C-81FZ8 GMCC compressor of the experiment in the high frequency and low frequency test and analysis the association with of the input power, exhaust pressure and suction pressure. Test and analysis the system heating capacity, COP in different frequency. Research shows that: keeping in the same test conditions, 25Hz of the low frequency range is as a low frequency energy-saving peak point, while 85Hz of the high frequency range is as an efficient operation peaks. Different compressor frequency has a greater influence on the size of the heat, and heat increases with the increasing of the frequency. The influences of the COP appear two parabolic peaks, respectively in the low and high frequency range. The system part load COP in a certain range of frequencies can achieve maximum, then will reduce the system performance.
出处 《建筑热能通风空调》 2014年第1期36-38,共3页 Building Energy & Environment
关键词 变频 频率 热泵空调 制热量 COP inverter, frequency, heat pump air-conditioning, heat capacity, COP
  • 相关文献

参考文献4

二级参考文献25

  • 1王起霄,刘淑静,汝长海.变频空调的性能研究[J].哈尔滨商业大学学报(自然科学版),2001,17(3):69-71. 被引量:16
  • 2孙玉清,李青,詹宗勉.压缩机变频能量调节控制冷库温度的研究[J].大连海事大学学报,1995,21(4):65-68. 被引量:1
  • 3Tassou S A,Marqunand C J,Wilson D R.Comparison of the performance of capacity controlled and conventional ON/OFF controlled heat pumps[J].Applied Energy,1983,5(4):241-256.
  • 4Vargas J V C.Simulation in transient regime of a heat pump with closed-loop and on-off control[J].International Journal of Refrigeration,1995,18(4):235-243.
  • 5Eckels S J.Evaporation and condensation of HCF-134a and CFC-12 in a smooth tube and a micro-fm tube[J].ASHRAE Trans,1991,97:71-81.
  • 6Sami S M,Tulej P J,Song B.Study of heat and mass characteristics of ternary non-azeotropic refrigerant mixtures inside air/refrigerant enhanced surface tubing[J].ASHRAE Trans,1995,101:1402-1412.
  • 7Slugem K.Enhancement of in-tube condensation of non-azeotropic refrigerant mixture with a micro-fin tube[J].Trans of the JAR,1993,10(1):95-101.
  • 8Masaaki T T O,Hideyaki K.Boiling heat transfer and pressure drop in internal spiral-grooved tubes[J].JSME,1979,22:171-173.
  • 9Youn Cheol Park, Young Chul Kim, Man-Ki Min, performance analysis on a multi-type inverter air conditioner, energy conversion and management, 2001, 42:1607--1621.
  • 10Salama M M. Dynamic model for thermal generation during change of load[J]. Energy conversion and management, 2001,41 : 299-- 309.

共引文献28

同被引文献47

引证文献5

二级引证文献15

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部