期刊文献+

建筑气密性与室内CO_2浓度的变化 被引量:1

Research of Building Air Tightness and Indoor CO_2 Concentration
下载PDF
导出
摘要 通过实验实测和理论计算结合的方法研究自然通风和机械通风状态下,室内CO2浓度与建筑气密性的关系。设计了窗户密闭和开启的三组建筑气密性工况,在室外环境条件相近的情况下,利用鼓风门法测试了室内的自然通风量,同时测定记录了室内的CO2浓度变化。利用实验结果结合全面通风计算理论,计算了机械通风情况下三组工况室内CO2浓度变化。结果表明,窗户微微开启(5°)相较房间密闭状态在自然通风情况下室内CO2浓度可下降20%;机械通风情况下可降低10%,同时,对空调耗电量影响较小,运行4.5 h仅相差0.05kW·h。 The methods of experimental measurements and theoretical calculation are used to research the relationship of indoor CO2 concentration and building air tightness in natural ventilation and mechanical ventilation, respectively. Three experimental conditions of windows closed and opened are designed. The blower door test method is used to test natural ventilation, and the indoor CO2 concentration is tested. The general ventilation theoretical calculation formula is used to calculate the indoor CO2 concentration of mechanical ventilation conditions. The results show that the indoor CO2 concentration difference of windows opened and closed is about 20% in natural ventilation, and it is 10% in mechanical ventilation.
出处 《实验室研究与探索》 CAS 北大核心 2014年第4期37-39,共3页 Research and Exploration In Laboratory
基金 上海大学生创新创业训练计划资助(SH2011101)
关键词 CO2浓度 建筑气密性 鼓风门法 CO2 concentration building air tightness blower door
  • 相关文献

参考文献11

二级参考文献25

  • 1张才才,李振海.上海市集合住宅气密性能实测及换气性能分析[J].节能,2005,24(2):35-37. 被引量:15
  • 2杨春红,王桂香,牛永泽.节能窗:建筑节能的“重头戏”[J].墙材革新与建筑节能,2005(8):39-39. 被引量:1
  • 3周燕,闫成文,姚健,张文宏.居住建筑外窗气密性对建筑能耗的影响[J].宁波大学学报(理工版),2007,20(2):248-250. 被引量:14
  • 4刘玉峰 胡振杰 等.公共建筑室内空气品质分析与控制方法.全国暖通空调制冷1996年学术年会资料集[M].,1996..
  • 5马仁民.地板送风气流分布影响热分布规律的研究[J].暖通空调,1985,15(3).
  • 6[1]Hiroshi Yoshino.Thermal Environment and IAQ Problem of Urban Residential Buildings in Japan and China.Shanghai 2003 HVAC Forum in China & Japan[J].pp.214-232,2003.11
  • 7[2]Hiroshi Yoshino.Shan Guan.Yu Fat Lun.et al.Indoor Thermal Environment of Urban Residential Buildings in China Summer Investigation in Three cities.International Workshop on Energy and Residential Buildings in China[J].pp.68-75,2002.10 kshop
  • 8[3]Pan Yougui.Li Nianping.et al.Field Measurement and Analysis of Indoor Thermal Environment of Changsha Urban Residential Buildings.EnerEnv'2003 Conference[J].pp.357-362,2003.10
  • 9[4]Zhu Kongmin.Li Nianping.et al.Field Measurement and Analysis of VOCs Concentration in Changsha Residential Buildings.EnerEnv'2003 Conference[J].pp.351-356,2003.10
  • 10[6]ASHRAE HANDBOOK[M].Fundamentals.Atlanta,2001

共引文献127